| 2018-10-10 12:27:00 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY |
| | NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR |
| | THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE |
| | APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12, |
| | 210.19, 215.2, 215.5, 310.15(B)(16), 408.4; WPB FBC |
| | 107.3.5 (ELECTRICAL SERVICES ARE EITHER 120/208 VOLT 3 |
| | PHASE, OR 120/240 VOLT 3 PHASE (WHICH HAS A HIGH LEG). |
| | INDICATION ON PLAN IS THAT THE SERVICE IS 230 VOLT 3 |
| | PHASE, BUT THERE ARE LOADS SHOWN ON B PHASE WHICH WOULD |
| | BE THE HIGH LEG. PROVIDE CLARIFICATION AND CORRECTIONS |
| | AS NEEDED TO ACCURATELY REFLECT THE INSTALLATION.) |
| | 2. CORRECTED FOR NEW RISER DIAGRAM. |
| | 3. PROVIDE MORE DETAIL FOR RISER DIAGRAM, SHOWING ALL |
| | DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD |
| | SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO |
| | ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| | 250.50, 250.94, 408.30 (THE PLAN SHOWS AN EXISTING |
| | RISER DIAGRAM WITH PANEL A AND PANEL A1, AND THEN SHOWS |
| | A SEPARATE RISER FOR PANEL B WHICH DOES NOT INCLUDE |
| | PANEL A AND PANEL A1 BE ADVISED THAT ONLY ONE SERVICE |
| | IS PERMITTED PER NEC 230.2 AND THE RISER DIAGRAM SHOULD |
| | REFLECT THIS TYPE OF INSTALLATION.) |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | (NOT PROVIDED.) |
| | 7. SHOW ON PLAN ALL LIGHTING AND POWER BRANCH CIRCUITS |
| | EXISTING AND THOSE TO BE INSTALLED. FBC 107.2.1 (NO |
| | LIGHTING CIRCUITS OR FIXTURES SHOWN.) |
| | 8. CORRECTED. |
| | 9. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2 (NOT |
| | PROVIDED - NO LIGHTING SHOWN.) |
| | 10. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED.) |
| | 11. CORRECTED. |
| | 12. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| | INDICATING THE REQUIRED SEPARATE PERMITS AND DATA |
| | SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS |
| | PRESENT. WPB FBC 105.1, 107.2.1 (NOT PROVIDED.) |
| | |
| | NEW COMMENTS: |
| | |
| | 13. LOCATION OF PANEL B SHOWN ON PLAN DOES NOT HAVE |
| | PROPER CLEARANCE REQUIRED. PROVIDE CORRECTION. NEC |
| | 110.26 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |