| 2018-04-10 13:20:51 | 1ST REVIEW FBC-2017 MECHANICAL, EXISTING BUILDING, |
| | ENERGY CONSERVATION CODES |
| | PERMIT #18031402 |
| | 4/10/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW, AND |
| | THERE ARE NO NOTES ON THE PLANS BY THE ARCHITECT TO |
| | INDICATE IF THERE ARE EXISTING HVAC SYSTEMS IN THE |
| | TENANT SPACE, OR HOW THE ROOMS AND SPACES ARE BEING |
| | VENTILATED. |
| | |
| | 2) ACCORDING TO THE BUILDING PLAN REVIEW COMMENTS THE |
| | PROPOSED PROJECT IS A CHANGE OF OCCUPANCY PER SECTION |
| | 202 FBC-17 EXISTING BUILDING CODE. PLEASE SEE SECTION |
| | 1009 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR |
| | ALL ROOMS AND SPACES PER TABLE 403.3.1 FBC-17 |
| | MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES THE |
| | REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. |
| | |
| | 3) REVISE THE PLAN TO SHOW ALL NEW MECHANICAL |
| | INSTALLATIONS, OR ALTERATIONS TO THE EXISTING SYSTEMS |
| | SUCH AS AC REPLACEMENTS, DUCT RELOCATIONS, DUCT |
| | EXTENSIONS, DIFFUSER OR GRILL REPLACEMENTS, EXHAUST OR |
| | O/A LOUVER INSTALLATIONS ETC. |
| | |
| | 3) BREWERY: A) CLARIFY IF A BOILER AND CHILLER WILL BE |
| | INSTALLED FOR USE IN THE BREWING PROCESS, AND PROVIDE |
| | EQUIPMENT SCHEDULES, EQUIPMENT LOCATIONS, AND DETAILS |
| | ON THE PLAN IF APPLICABLE. B) PROVIDE A PROCESS PIPING |
| | LAYOUT AND ISOMETRIC DRAWING AND INCLUDE PIPE SPECS. D) |
| | IDENTIFY AND LABEL ALL BREWERY TANKS, EQUIPMENT ETC. |
| | |
| | 4) ADVISORY: PLEASE NOTE THAT A CHANGE OF OCCUPANCY MAY |
| | BE REQUIRED TO SHOW COMPLIANCE WITH SECTION C505.1 |
| | FBC-17 ENERGY CONSERVATION, IN WHICH CASE ENERGY |
| | CALCULATIONS WILL HAVE TO BE SUBMITTED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. PLEASE NOTE THAT |
| | ADDITIONAL COMMENTS MAY OCCUR WHEN CORRECTED PLANS ARE |
| | SUBMITTED FOR REVIEW. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |