2018-04-10 13:20:511ST REVIEW FBC-2017 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #18031402
 4/10/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW, AND
 THERE ARE NO NOTES ON THE PLANS BY THE ARCHITECT TO
 INDICATE IF THERE ARE EXISTING HVAC SYSTEMS IN THE
 TENANT SPACE, OR HOW THE ROOMS AND SPACES ARE BEING
 VENTILATED.
  
 2) ACCORDING TO THE BUILDING PLAN REVIEW COMMENTS THE
 PROPOSED PROJECT IS A CHANGE OF OCCUPANCY PER SECTION
 202 FBC-17 EXISTING BUILDING CODE. PLEASE SEE SECTION
 1009 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR
 ALL ROOMS AND SPACES PER TABLE 403.3.1 FBC-17
 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 3) REVISE THE PLAN TO SHOW ALL NEW MECHANICAL
 INSTALLATIONS, OR ALTERATIONS TO THE EXISTING SYSTEMS
 SUCH AS AC REPLACEMENTS, DUCT RELOCATIONS, DUCT
 EXTENSIONS, DIFFUSER OR GRILL REPLACEMENTS, EXHAUST OR
 O/A LOUVER INSTALLATIONS ETC.
  
 3) BREWERY: A) CLARIFY IF A BOILER AND CHILLER WILL BE
 INSTALLED FOR USE IN THE BREWING PROCESS, AND PROVIDE
 EQUIPMENT SCHEDULES, EQUIPMENT LOCATIONS, AND DETAILS
 ON THE PLAN IF APPLICABLE. B) PROVIDE A PROCESS PIPING
 LAYOUT AND ISOMETRIC DRAWING AND INCLUDE PIPE SPECS. D)
 IDENTIFY AND LABEL ALL BREWERY TANKS, EQUIPMENT ETC.
  
 4) ADVISORY: PLEASE NOTE THAT A CHANGE OF OCCUPANCY MAY
 BE REQUIRED TO SHOW COMPLIANCE WITH SECTION C505.1
 FBC-17 ENERGY CONSERVATION, IN WHICH CASE ENERGY
 CALCULATIONS WILL HAVE TO BE SUBMITTED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS. PLEASE NOTE THAT
 ADDITIONAL COMMENTS MAY OCCUR WHEN CORRECTED PLANS ARE
 SUBMITTED FOR REVIEW.
  