Plan Review Notes
Plan Review Notes For Permit 18031395
Permit Number 18031395
Review Stop B
Sequence Number 4
Notes
Date Text
2019-12-04 11:21:10 
 REVISED 12/04/19 AND RESPONDED E-MAIL TO PAUL HALL
 (CONTRACTOR) PROVIDING CLARIFICATIONS. JG.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
  
  
 CONSTRUCTION OF NEW OFFICE/WAREHOUSE STRUCTURE. THIRD
 BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  
 2- OK
  
 ORIGINAL COMMENT.
 3- SHEET LS-1:
 A) TYPE III-B CONSTRUCTION TYPE SPECIFIED IN THE DESIGN
 CRITERIA REQUIRES 2 HR FIRE RESISTANCE RATING FOR THE
 EXTERIOR WALLS. SEE BY TABLE 601 FBC-BUILDING. PROVIDE
 COMPLETE DETAIL/SPECIFICATIONS SHOWING COMPLIANCE WITH
 THE 2 HR FIRE RATED ASSEMBLY.
  
 RESPONSE:
 THE REVISED PLANS SPECIFY 2 HOUR WALL FOR THE SOUTH AND
 EAST EXTERIOR WALLS ONLY. THIS IS INCORRECT. IF THE
 CONSTRUCTION TYPE IS III-B, THEN ALL 4 EXTERIOR BEARING
 WALLS OF THIS BUILDING NEED TO BE 2 HOUR. REVISE PLANS
 AS REQUIRED.
 ALSO, PROVIDE COMPLETE WALL DETAIL OF THE SPECIFIED 2
 HOUR WALL ASSEMBLY U905. NO DETAIL WAS PROVIDED AS
 REQUESTED ON PREVIOUS CHECKLISTS.
  
  
 4- OK.
 5- FBC-ACCESSIBILITY.
 A) OK
 B) OK
 C)OK
  
 ORIGINAL COMMENT:
 6- LOCATION OF ATTIC ACCESS DOESN'T SEEM TO PROVIDE THE
 MIN. 30" CLEAR HEADROOM AS REQUIRED BY SEC. 1209.2 FBC.
 REVISE AS REQUIRED.
  
 RESPONSE (REVISED 12/04/19 FOR CLARIFICATION):
 SECOND FLOOR CEILING WAS REPLACED WITH 2' X 4'
 ACOUSTICAL CEILING. NEED TO REVISE DETAILS W2 AND W3 ON
 SHEET LS-1 TO MATCH NEW CEILING SPECIFICATIONS. SEC.
 107.2.1 CITY AMENDMENTS.
  
 7- OK.
 8- OK
 9- OK.
 10- OK
  
 11- ENERGY CALCULATIONS:
 ORIGINAL COMMENT:
 A) ARCHITECT OF RECORD TO CERTIFY (SIGNATURE AND
 LICENSE NUMBER) ON ENERGY FORM AS REQUIRED BY SEC.
 C103.1.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. ARCHITECT'S RESPONSE LETTER STATES THAT
 A SIGNATURE WAS PROVIDED. THERE ARE NO SIGNATURES OF
 THE ARCHITECT ON THE ENERGY FORMS SUBMITTED.
 ALSO, ACCORDING TO PLANS SUBMITTED, IT LOOKS LIKE THE
 ARCHITECT IS DESIGNING THE BUILDING, ELECTRICAL AND
 PLUMBING SYSTEMS. PROVIDE SIGNATURE AND LICENSE NUMBERS
 ON EACH TRADE THE ARCHITECT IS RESPONSIBLE FOR THE
 DESIGN.
 NOTE: AT THE BOTTOM OF THE CERTIFICATIONS PAGE THERE IS
 A FOOTNOTE STATING THAT THE NAMES AND REGISTRATION
 NUMBERS MAY BE USED WHERE ALL THE INFORMATION IS
 CONTAINED IN THE SIGNED AND SEALED PLANS. THIS MAY BE
 DONE ALSO. BUT MAKE SURE EACH TRADE IS SHOWING THE
 DESIGNER OF RECORD.
  
 NEW COMMENT BASED ON CERTIFICATION PAGE SUBMITTED AT
 THIS TIME:
 THE OWNER SIGNED ON THE OWNER/AGENT SPACE LAST TIME.
 THIS TIME THIS SPACE WAS SIGNED BY SOMEONE ELSE. ONLY
 THE OWNER, THE OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNED BY THE OWNER CAN SIGN THE FORM.
 OWNER NEEDS TO SIGN THE FORM OR SINCE THE PERSON
 SIGNING ON THIS SPACE IS NOT THE ARCHITECT, THEN
 PROVIDE PROOF THAT THE PERSON SIGNING THE FORM IS THE
 OWNER'S LEGALLY DESIGNATED AGENT AS REQUIRED BY SEC.
 C103.2 FBC-ENERGY CONSERVATION.
  
  
 B) OK.
 C) OK
 D) OK
  
 ORIGINAL COMMENT:
 E)PLANS WERE REVISED. LOCATION OF WINDOWS CHANGED.
 REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 NOT ADDRESSED. NOW THERE IS NOT INFORMATION FOR THE
 WINDOWS. PROVIDE COMPLETE INFORMATION. SEC. 107.2.1
 CITY AMENDMENTS.
  
  
 12- OK.
 13- OK.
 14- OK.
  
 ORIGINAL COMMENT:
 15- FLAT ROOF NOA 14-0627.05 SUBMITTED: CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 1609.1 FBC. NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED
 AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 THIS WILL BE A PROVISO. THE INFORMATION WILL NEED TO BE
 PROVIDED FOR REVIEW PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 15(1)- PROVIDE ICC EVALUATION REPORT FOR ICYNENE SPRAY
 INSULATION SPECIFIED ON PLANS. AND ARCHITECT OF RECORD
 TO REVIEW/APPROVE PRIOR T SUBMITTAL. SEC. 2603 FBC.
  
 RESPONSE:
 THIS WILL BE A PROVISO. THE INFORMATION WILL NEED TO BE
 PROVIDED FOR REVIEW PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS.
  
  
 16- OK.
 17- OK.
  
 18- TRUSS PACKAGE (REVISED 12/04/19):
 IT IS MY UNDERSTANDING THAT TRUSS TO TRUSS CONNECTIONS
 ARE THE RESPONSIBILITY OF THE TRUSS ENGINEER (ANSI/TPI
 1). NOTE #9 OF HIP GIRDER A10 AND NOTE # 6 OF FLOOR
 GIRDER FG1 SPECIFY THAT THE SELECTION OF CONNECTORS IS
 THE RESPONSIBILITY OF OTHERS. THESE ARE TRUSS TO TRUSS
 CONNECTIONS, THEREFORE THE TRUSS ENGINEER NEEDS TO
 SPECIFY THE CONNECTORS AND PROPERLY SIGN AND SEAL THE
 SHEETS WERE CONNECTOR IS SPECIFIED.
 ARCHITECT RESPONSE LETTER STATES THAT "SEE DETAIL
 1/LS-1 FOR DETAIL, AND ATTACHED TRUSS PACKAGE". THIS
 DETAIL IS INCORRECT. THE HANGERS ARE NOT BY THE TRUSS
 COMPANY. THEY ARE THE RESPONSIBILITY OF THE TRUSS
 ENGINEER.
  
 19- DESIGNER OF RECORD TO REVIEW REVISED TRUSS PACKAGE,
 INCLUDING INDIVIDUAL TRUSSES BEFORE SUBMITTAL TO THIS
 OFFICE. SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: THIS APPLIES ONCE TRUSS PACKAGE ITEMS ARE
 CORRECTED.
  
 20- OK.
  
 21- WELDED OR BOLTED CONNECTIONS (FYI)
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712