| Plan Review Notes For Permit 18031395 |
| Permit Number |
18031395 |
|
| Review Stop |
R |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2019-11-26 18:51:51 | NOTE: | | | THIS WILL BE A PROVISO. THE INFORMATION WILL NEED TO BE | | | PROVIDED FOR REVIEW PRIOR TO INSPECTIONS TO AVOID | | | CONFLICTS/DELAYS. | | | | | | | | | 1- FLAT ROOF NOA 14-0627.05 SUBMITTED: CLEARLY MARK | | | WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO | | | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | | 1609.1 FBC. NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET | | | THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED | | | AND SEALED RAS 117 CALCULATIONS ARE REQUIRED. | | | | | | RESPONSE: | | | APPROVED ASSEMBLY WAS NOT MARKED/IDENTIFIED. APPROVED | | | ASSEMBLIES ARE ON PAGE 5 OF 8 TO PAGE 7 OF 8. NOTE: ALL | | | THESE ASSEMBLIES ARE FOR ASSEMBLIES WITH INSULATION. | | | PLANS DON'T SHOW ANY FLAT ROOF ASSEMBLY WITH ADDITIONAL | | | INSULATION. THE INSULATION SHOWN ON PLANS IS FOR | | | ICYNENE INSULATION SPRAYED AT THE BOTTOM OF ROOD DECK. | | | IF USING A FLAT ROOF ASSEMBLY WITH ADDITIONAL | | | INSULATION , THEN ARCHITECTURAL PLANS NEED TO BE | | | REVISED SHOWING THE ADDITIONAL INSULATION. SEC. 107.2.1 | | | CITY AMENDMENTS. | | | | | | | | | APPROVED: | | | SHINGLES FL18355-R4. |
|