| Plan Review Notes For Permit 18031395 |
| Permit Number |
18031395 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2019-12-05 12:23:29 | PLUMBING COMMENTS: APPROVED WITH PROVISO | | | 1. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE | | | AS A DEFERRED SUBMITTAL, A CODE COMPLIANT SANITARY | | | ISOMETRIC THAT SHOWS THE DRINKING FOUNTAIN AND THE MOP | | | SINK DOWNSTREAM OF THE WET VENT IN ACCORDANCE WITH FBC | | | PL 912.1. PROVIDE A VENT FOR THE DRINKING FOUNTAIN PER | | | FBC PL 909.1 AND 909.2. THE DOCUMENTS SHALL BE | | | SUBMITTED, APPROVED AND ON SITE PRIOR TO FIRST | | | INSPECTION. PROCEED AT YOUR OWN RISK. | | | 2. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE | | | AS A DEFERRED SUBMITTAL, AN ENGINEERED DETAIL OF THE | | | SUPPORT SYSTEM FOR THE WATER HEATER. THE DOCUMENTS | | | SHALL BE SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL | | | INSPECTION. PROCEED AT YOUR OWN RISK. | | | 3. WATER HAMMER ARRESTOR SHALL BE INSTALLED WHERE QUICK | | | CLOSING VALVES ARE UTILIZED PER FBC PL 604.9 | | | 4. FULL OPEN VALVES SHALL BE INSTALLED ON TOP OF EVERY | | | WATER DOWNFEED PIPE PER FBC PL 604.9. |
|