Plan Review Notes
Plan Review Notes For Permit 18031395
Permit Number 18031395
Review Stop M
Sequence Number 3
Notes
Date Text
2019-12-06 15:34:312ND REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 PERMIT #18031395
 12/6/19
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IT APPEARS THE ORIGINAL AC CALCULATIONS HAVE BEEN
 VOIDED OUT, HOWEVER NO NEW AC CALCULATIONS HAVE BEEN
 SUBMITTED- SECTION C403.2.1 FBC EC.
  
 2) A REVISED ENERGYGAUGE COMPLIANCE REPORT HAS BEEN
 SUBMITTED, HOWEVER THERE ARE MSSING CERTIFICATIONS ON
 PAGE 4. PLEASE REFER TO BUILDING REVIEW COMMENT #11
 (12/4/2019) FOR COMPLIANCE REQUIRMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  