| Plan Review Notes For Permit 18031395 |
| Permit Number |
18031395 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2019-12-06 15:34:31 | 2ND REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION | | | PERMIT #18031395 | | | 12/6/19 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) IT APPEARS THE ORIGINAL AC CALCULATIONS HAVE BEEN | | | VOIDED OUT, HOWEVER NO NEW AC CALCULATIONS HAVE BEEN | | | SUBMITTED- SECTION C403.2.1 FBC EC. | | | | | | 2) A REVISED ENERGYGAUGE COMPLIANCE REPORT HAS BEEN | | | SUBMITTED, HOWEVER THERE ARE MSSING CERTIFICATIONS ON | | | PAGE 4. PLEASE REFER TO BUILDING REVIEW COMMENT #11 | | | (12/4/2019) FOR COMPLIANCE REQUIRMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|