Plan Review Notes
Plan Review Notes For Permit 18031395
Permit Number 18031395
Review Stop P
Sequence Number 2
Notes
Date Text
2019-03-12 13:39:14PLUMBING PROVISO:(1) PROVIDE A CODE COMPLIANT
 SANITARY ISOMETRIC DRAWING BY 1ST INSPECTION THAT
 SHOW THE MOP SINK DOWN STREAM OF THE WET VENT.
 FBC-P 107.3.5*FBC-P 912.1.(2) HAMMER ARRESTOR
 MUST BE INSTALLED WHERE QUICK CLOSING VALVES
 ARE UTILIZED. FBC-P 604.9 (3) FULL OPEN SHUT OFF
 VALVES SHALL BE INSTALLED ON-TOP OF EVERY WATER
 DOWN FEED PIPE. FBC-P 604.9
  
  