| 2019-03-21 12:33:57 | 2ND REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION | | | PERMIT #18031395 | | | 3/21/19 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE MECHANICAL PLANS SHALL BEAR THE SIGNATURE OF THE | | | INSTALLING CONTRACTOR (KYZAR AIR CONDITIONING INC.) OR | | | SHALL BE SIGNED AND SEALED BY A FL. LICENSED ENGINEER- | | | SECTION 105.3.1.2 WPB AMENDMENTS TO THE FBC-17. | | | | | | 2) SHEET M.1: IT APPEARS THE AIR HANDLER WILL BE | | | INSTALLED IN THE ATTIC WHICH IS NOT ALLOWED IN A | | | COMMERCIAL BUILDING- SECTION C403.2.9.6 FBC EC. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|