Plan Review Notes
Plan Review Notes For Permit 18031395
Permit Number 18031395
Review Stop M
Sequence Number 2
Notes
Date Text
2019-03-21 12:33:572ND REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 PERMIT #18031395
 3/21/19
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL PLANS SHALL BEAR THE SIGNATURE OF THE
 INSTALLING CONTRACTOR (KYZAR AIR CONDITIONING INC.) OR
 SHALL BE SIGNED AND SEALED BY A FL. LICENSED ENGINEER-
 SECTION 105.3.1.2 WPB AMENDMENTS TO THE FBC-17.
  
 2) SHEET M.1: IT APPEARS THE AIR HANDLER WILL BE
 INSTALLED IN THE ATTIC WHICH IS NOT ALLOWED IN A
 COMMERCIAL BUILDING- SECTION C403.2.9.6 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  