Plan Review Notes
Plan Review Notes For Permit 18031395
Permit Number 18031395
Review Stop B
Sequence Number 2
Notes
Date Text
2019-03-14 18:17:21 
 CONSTRUCTION OF NEW OFFICE/WAREHOUSE STRUCTURE. SECOND
 BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
  
 1- IMPACT FEES - PAPER SUBMITTALS
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 ORIGINAL COMMENT:
 2- PROVIDE SITE GRADING PLAN (INCLUDING PROPOSED LOT
 DRAINAGE) SHOWING COMPLIANCE WITH SEC. 1804.4
 FBC-BUILDING AND SEC. 107.2.5 CITY AMENDMENTS.
 NOTE: DRAWINGS REFERENCED ON GENERAL SITE NOTE #5 ON
 SHEET SP-1 WERE NOT SUBMITTED. ALSO, COORDINATED
 DRAWINGS WITH PROPOSED RETAINING WALLS TO AVOID
 CONFLICTS/DELAYS. SEE SHEET SP-1.
  
 RESPONSE:
 A) ONLY ON SET OF CIVIL DRAWINGS WAS SUBMITTED. NEED
 TWO COPIES. SEC. 107.1 CITY AMENDMENTS.
  
 B) IT LOOKS LIKE THREE IS A CONFLICT BETWEEN THE CIVIL
 DRAWINGS AND ARCHITECTURAL DRAWINGS REGARDING THE
 RETENTION WALLS. THERE ARE TWO DIFFERENT TYPE OF
 RETENTION WALLS. CLARIFY/REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT.
 3- SHEET LS-1:
 A) TYPE III-B CONSTRUCTION TYPE SPECIFIED IN THE DESIGN
 CRITERIA REQUIRES 2 HR FIRE RESISTANCE RATING FOR THE
 EXTERIOR WALLS. SEE BY TABLE 601 FBC-BUILDING. PROVIDE
 COMPLETE DETAIL/SPECIFICATIONS SHOWING COMPLIANCE WITH
 THE 2 HR FIRE RATED ASSEMBLY.
  
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER STATES "TYPE III-B
 CONSTRUCTION AS NOTED WILL ALLOW THE 2-STRY OFFICE.
 EXTERIOR WALL SHALL BE 2HR. PROTECTED". THIS DOESN'T
 ADDRESS THE REQUIRED 2 HOUR WALL FOR TYPE III
 CONSTRUCTION. PLANS DON'T SHOW ANY DETAILS AND
 SPECIFICATIONS FOR TWO HOUR CONCRETE BLOCK WALLS. NOT
 ALL CONCRETE BLOCK IS TWO HOUR RATED.
  
 ORIGINAL COMMENT:
 B) SQUARE FEET OF ALLOWED OPENINGS SPECIFIED IN THE
 DESIGN CRITERIA DON'T MATCH PLANS. REVISE AS REQUIRED
 TO MATCH. SEC. 705.8 FBC-BUILDING.
  
 RESPONSE:
 OPENINGS LOCATION WERE REVISED. IT LOOKS LIKE
 INFORMATION GIVEN IS FOR THE WEST WALL. IF SO, IS
 MISSING THE DOOR OPENING ON THE FIRST FLOOR. REVISE AS
 REQUIRED.
  
 C) OK.
  
 ORIGINAL COMMENT:
 D) REVISE THE GENERAL BUILDING LIMITATIONS INFORMATION
 SHOWN IN THE DESIGN CRITERIA. TABLE 503 IS INCORRECT.
 THIS BUILDING HAS A MIXED OCCUPANCY. NEED TO PROVIDE
 INFORMATION FOR EACH OCCUPANCY. USE TABLE 504.3, TABLE
 504.4 AND TABLE 506.2 FBC 2017 FOR CORRECT AND CURRENT
 CODE INFORMATION AND REVISE AS REQUIRED.
  
 RESPONSE:
 THIS WILL BE REVIEWED BASED ON THE CLARIFICATION
 REQUIRED BY ITEM #3(A) ABOVE REGARDING CONSTRUCTION
 TYPE.
  
 E) OK.
  
 F) OK.
  
 G) OK.
  
 4- OK.
  
 5- FBC-ACCESSIBILITY.
 A) OK
 B) OK
 C)OK
  
 ORIGINAL COMMENT:
 A) PROVIDE COMPLIANCE WITH THE VERTICAL ACCESSIBILITY
 REQUIREMENTS FOR THE SECOND STORY OFFICE AS REQUIRED BY
 SEC. 201.1.1 FBC-ACCESSIBILITY. OR SHOW IN PLANS
 COMPLIANCE WITH ANY EXCEPTION.
  
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER STATES "201.1.1(3) OCCUPANT
 LOAD LESS THAN 5 PERSONS: SO NOTED ON THE PLAN". PLANS
 DON'T SHOW COMPLIANCE WITH THIS EXCEPTION. THERE ARE
 TWO REQUIREMENTS TO MEET THIS EXCEPTION. FIRST OF ALL,
 IT NEEDS TO BE CLEAR THAT THE OFFICE IS NOT OPEN TO THE
 PUBLIC. THE SECOND REQUIREMENTS IS THAT IT CAN NO HOUSE
 MORE THAN 5 PERSONS. ONLY THE SECOND REQUIREMENT WAS
 MET BY THE SIZE OF THE OFFICE. IN ORDER TO APPLY THIS
 EXCEPTION IT MUST BE CLEARLY NOTED ON PLANS BY THE
 OFFICE AREA THAT THE OFFICE CAN NOT OPEN TO THE PUBLIC.
 REVISE PLANS AS REQUIRED.
  
 ORIGINAL COMMENT:
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 ACCESSIBLE ROUTE SHOWING COMPLIANCE WITH SEC.
 206-FBC-ACCESSIBILITY.
 ACCESSIBLE ROUTE FROM PARKING TO THE BUILDING ENTRANCE
 (SEC. 402 AND SEC. 404 FBC-ACCESSIBILITY).
  
 RESPONSE:
 THE BUILDING MAIN ENTRANCE DOESN'T SEEM TO COMPLY. SHOW
 COMPLIANCE WITH THE CHANGE OF LEVEL AT THE ENTRANCE.
 SHOW MANEUVERING CLEARANCES (INCLUDING TURNING
 CLEARANCES) AT THE VESTIBULE AREA LEADING TO THE
 WAREHOUSE AREA.
  
 ORIGINAL COMMENT:
 C)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 STAIRWAY SHOWING COMPLIANCE WITH ALL THE REQUIREMENTS
 OF SEC. 504-FBC-ACCESSIBILITY.
 INCLUDE THE NOSING SPECIFICATIONS.
  
 RESPONSE:
 REVISE NOSING DETAIL ON SHEET A-2. THE UNDERSIDE OF
 NOSING NEEDS TO COMPLY WITH SEC. 504.5
 FBC-ACCESSIBILITY.
  
 ORIGINAL COMMENT:
 6- LOCATION OF ATTIC ACCESS DOESN'T SEEM TO PROVIDE THE
 MIN. 30" CLEAR HEADROOM AS REQUIRED BY SEC. 1209.2 FBC.
 REVISE AS REQUIRED.
  
 RESPONSE:
 ATTIC ACCESS WAS REMOVED. ATTIC ACCESS IS REQUIRED BY
 SEC. 1209.2 FBC.
  
 7- SHEET A-1:
 A) OK.
  
 B) OK.
  
 8- OK.
  
 9- OK.
  
 10- SOIL TEST REPORT:
 A) OK.
  
 B) OK.
  
 C) OK.
  
 D) OK.
  
 11- ENERGY CALCULATIONS:
 ORIGINAL COMMENT:
 A) ARCHITECT OF RECORD TO CERTIFY (SIGNATURE AND
 LICENSE NUMBER) ON ENERGY FORM AS REQUIRED BY SEC.
 C103.1.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER STATES "CERTIFICATION WITH
 NAME AND LICENSE NUMBER SHOWN". ENERGY CALCULATIONS
 SUBMITTED DON'T HAVE THE SIGNATURE AND LICENSE NUMBER
 OF THE ARCHITECT. ACCORDING TO PLANS SUBMITTED, IT
 LOOKS LIKE THE ARCHITECT IS DESIGNING THE BUILDING,
 ELECTRICAL AND PLUMBING SYSTEMS. PROVIDE SIGNATURE AND
 LICENSE NUMBERS ON EACH TRADE AS REQUIRED.
  
 B) OK.
  
 ORIGINAL COMMENT:
 C) REVISE BUILDING ORIENTATION SHOWN ON PAGE 17 OF 22
 TO MATCH PLANS. NOTE: PLANS ARE DRAWN WITH NORTH ARROW
 POINTING SOUTH.
  
 RESPONSE:
 WHY ARE THERE TWO EAST WALLS?
  
 ORIGINAL COMMENT:
 D) REVISE WALL TYPES AND INSULATION INFORMATION SHOWN
 ON PAGE 17 OF 22 TO MATCH PLANS. ALSO, NEED TO PROVIDE
 INFORMATION FOR RAISED FLOOR ABOVE THE FIRST FLOOR
 UNCONDITIONED WAREHOUSE AREA. NOTE: COORDINATE WITH
 ARCHITECT.
  
 RESPONSE:
 WHY ARE THERE TWO EAST WALLS?.
 PAGE 19 OF 22 DOESN'T SHOW ANY INFORMATION FOR THE
 RAISED FLOOR ABOVE WAREHOUSE.
  
 NEW COMMENT:
 E)PLANS WERE REVISED. LOCATION OF WINDOWS CHANGED.
 REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE SHGC FACTOR
 SPECIFIED IN THE ENERGY CALCULATIONS WILL BE REQUIRED
 FOR INSPECTION.
  
  
 12- OK.
  
 13- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
 A) OK.
  
 B) OK.
  
 14- OK.
  
 ORIGINAL COMMENT:
 15- FLAT ROOF NOA 14-0627.05 SUBMITTED: CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 1609.1 FBC. NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED
 AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 APPROVED ASSEMBLY WAS NOT MARKED/IDENTIFIED. APPROVED
 ASSEMBLIES ARE ON PAGE 5 OF 8 TO PAGE 7 OF 8. NOTE: ALL
 THESE ASSEMBLIES ARE FOR ASSEMBLIES WITH INSULATION.
 PLANS DON'T SHOW ANY FLAT ROOF ASSEMBLY WITH ADDITIONAL
 INSULATION. THE INSULATION SHOWN ON PLANS IS FOR
 ICYNENE INSULATION SPRAYED AT THE BOTTOM OF ROOD DECK.
 IF USING A FLAT ROOF ASSEMBLY WITH ADDITIONAL
 INSULATION , THEN ARCHITECTURAL PLANS NEED TO BE
 REVISED SHOWING THE ADDITIONAL INSULATION. SEC. 107.2.1
 CITY AMENDMENTS.
  
 NEW COMMENT ( I APOLOGIZE . I FORGOT TO ASK FOR IT ON
 THE PREVIOUS REVIEW):
 15(1)- PROVIDE ICC EVALUATION REPORT FOR ICYNENE SPRAY
 INSULATION SPECIFIED ON PLANS. AND ARCHITECT OF RECORD
 TO REVIEW/APPROVE PRIOR T SUBMITTAL. SEC. 2603 FBC.
  
 16- OK.
  
 17- OK.
  
 18- TRUSS PACKAGE:
 A)OK.
  
 B)OK.
  
 ORIGINAL COMMENT:
 C) TRUSS PACKAGE COVER LETTER NEEDS TO PROVIDE THE
 INFORMATION OF THE PROFESSIONAL DESIGNER OF RECORD AS
 REQUIRED BY FAC 61G15-23.003.
  
 RESPONSE.
 NOT RESPONSE. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 D) TRUSS LAYOUT SHOW THE TRUSS TO TRUSS STRUCTURAL
 CONNECTORS. TRUSS ENGINEER TO SIGN AND SEAL TRUSS
 LAYOUT AND PROVIDE HIS INFORMATION AS REQUIRED BY FAC
 61G15-23.001. OR PROVIDE COMPLETE STRUCTURAL
 CONNECTIONS ON EACH INDIVIDUAL TRUSS DRAWING.
  
 RESPONSE:
 NOT ADDRESSED. TRUSS LAYOUT SHOW THE FLOOR TRUSS
 CONNECTORS RESTING ON THE FLOOR GIRDER. AND THERE ARE
 NOT CONNECTORS SPECIFIED ON THE INDIVIDUAL TRUSSES
 RESTING ON THE HIP GIRDER AND DIAGONAL HIP GIRDER. NOTE
 #9 OF INDIVIDUAL TRUSSES STATES THAT "HE
 DESIGN/SELECTION OF SUCH CONNECTION DEVICE(S) IS THE
 RESPONSIBILITY OF OTHERS". WHY? ISN'T THE TRUSS TO
 TRUSS CONNECTIONS THE RESPONSIBILITY OF THE TRUSS
 ENGINEER OF RECORD?. ALL STRUCTURAL CONNECTORS
 SPECIFIED NEED TO HAVE THE SEAL AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 E)OK.
  
 19- DESIGNER OF RECORD TO REVIEW REVISED TRUSS PACKAGE,
 INCLUDING INDIVIDUAL TRUSSES BEFORE SUBMITTAL TO THIS
 OFFICE. SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: THIS APPLIES ONCE TRUSS PACKAGE ITEMS ARE
 CORRECTED.
  
 ORIGINAL COMMENT:
 20- VALUE DECLARED I THE PERMIT APPLICATION IS TOO LOW.
 REVISE AS REQUIRED. SEC. 109.3 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. VALUATION TO INCLUDE ALL
 LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND
 DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $155,360. THE
 PERMIT FEE BALANCE IS $3250.30.
  
 21- WELDED OR BOLTED CONNECTIONS (FYI)
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 22-PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR
 REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW
 COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
 NOTE: ENTER BUILDING INFORMATION ON FRONT SCREEN FIELDS
 WHEN PLANS ARE REVISED SHOWING CORRECT CONSTRUCTIOIN
 TYPE AND RESUBMITTED. JG.
  