| 2018-05-02 10:00:21 | 1ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION |
| | PERMIT #18031395 |
| | 5/2/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) A-2: THERMAL ENVELOPE AND CONTINUOUS AIR BARRIER |
| | INCOMPLETE AT THE INTERSECTION OF THE FLOOR TRUSSES AND |
| | THE EXTERIOR WALL- SECTIONS C407.2, C402.5, AND |
| | C402.5.1. PLEASE NOTE THAT THE PLANS ARE SPECIFYING |
| | FOIL BACKED INSULATION ON THE EXTERIOR WALL AND THE |
| | ENERGY CALCULATIONS ARE INDICATING 3/4" ISO. |
| | |
| | 2) THE ENERGY AND AC CALCULATIONS ARE SPECIFYIONG THE |
| | CONDITIONED AREA AT 709 SQ. FT. HOWEVER THE THERMAL |
| | ENVELOPE APPEARS TO BE INCOMPLETE BECAUSE NO SECOND |
| | FLOOR INSULATION IS SHOWN ON THE PLAN OR IN THE CALCS. |
| | |
| | 3) AC-1: PROVIDE MINIMUM VENTILATION CALCULATIONS IN |
| | ACCORDANCE WITH TABLE 403.1.1. INDICATE THE REQUIRED |
| | AND PROVIDED CFMS OF OUTDOOR AIR. |
| | |
| | 4) AC-1: EXHAUST VENTILATION IS REQUIRED FOR THE TOILET |
| | ROOMS- TABLE 403.1.1. |
| | |
| | 5) AC-1: NATURAL OR MECHANICAL VENTILATION IS REEQUIRED |
| | FOR THE WAREHOUSE PER SECTION 401.2. PLEASE INDICATE |
| | WHICH METHOD IS TO BE USED AND PROVIDE A CALCULATION- |
| | SEE SECTION 402.2 AND TABLE 403.1.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |