2018-05-10 18:06:15CONSTRUCTION OF NEW OFFICE/WAREHOUSE STRUCTURE.
 BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
 2- PROVIDE SITE GRADING PLAN (INCLUDING PROPOSED LOT
 DRAINAGE) SHOWING COMPLIANCE WITH SEC. 1804.4
 FBC-BUILDING AND SEC. 107.2.5 CITY AMENDMENTS.
 NOTE: DRAWINGS REFERENCED ON GENERAL SITE NOTE #5 ON
 SHEET SP-1 WERE NOT SUBMITTED. ALSO, COORDINATED
 DRAWINGS WITH PROPOSED RETAINING WALLS TO AVOID
 CONFLICTS/DELAYS. SEE SHEET SP-1.
  
 3- SHEET LS-1:
 A) TYPE III-B CONSTRUCTION TYPE SPECIFIED IN THE DESIGN
 CRITERIA REQUIRES 2 HR FIRE RESISTANCE RATING FOR THE
 EXTERIOR WALLS. SEE BY TABLE 601 FBC-BUILDING. PROVIDE
 COMPLETE DETAIL/SPECIFICATIONS SHOWING COMPLIANCE WITH
 THE 2 HR FIRE RATED ASSEMBLY.
  
 B) SQUARE FEET OF ALLOWED OPENINGS SPECIFIED IN THE
 DESIGN CRITERIA DON'T MATCH PLANS. REVISE AS REQUIRED
 TO MATCH.
 SEC. 705.8 FBC-BUILDING.
  
 C) TABLE 1004.1.2 OCCUPANT LOAD FOR WAREHOUSES IS 500
 GROSS. PROVIDE JUSTIFICATION WHY IN THE DESIGN CRITERIA
 IS USING AN OCCUPANT LOAD OF 300. REVISE AS REQUIRED.
  
 D) REVISE THE GENERAL BUILDING LIMITATIONS INFORMATION
 SHOWN IN THE DESIGN CRITERIA. TABLE 503 IS INCORRECT.
 THIS BUILDING HAS A MIXED OCCUPANCY. NEED TO PROVIDE
 INFORMATION FOR EACH OCCUPANCY. USE TABLE 504.3, TABLE
 504.4 AND TABLE 506.2 FBC 2017 FOR CORRECT AND CURRENT
 CODE INFORMATION AND REVISE AS REQUIRED.
  
 E) REVISE ARRANGEMENTS AND NUMBER OF EXITS INFORMATION
 SHOWN IN THE DESIGN CRITERIA. SINGLE EXITS ARE ALLOWED.
 SEE SEC. 1006.3.2.1 AND TABLE 1006.3.2(2) FOR MIXED
 OCCUPANCIES AND REVISE NUMBER OF EXITS AND TRAVEL
 DISTANCE AS REQUIRED.
  
 F) REVISE TRAVEL DISTANCES LINES SHOWN ON THE LIFE
 SAFETY PLAN.
 (1) THE PATH IS MEASURED FROM THE MOST REMOTE POINT TO
 THE ENTRANCE TO THE EXIT. SEC. 1017.3 FBC. A DIAGONAL
 LINE IS NOT ACCEPTABLE. NEED TO CONSIDER PATH WHERE
 FURNITURE IS IN PLACE. TYPICALLY TRAVEL DISTANCE IS
 SHOWN GOING PARALLEL TO THE WALLS. PROVIDE FURNITURE
 LAYOUT AND REDRAW TRAVEL DISTANCES AS REQUIRED.
  
 (2) PROVIDE A SEPARATE TRAVEL DISTANCE FROM THE MOST
 REMOTE POINT OF THE WAREHOUSE TO THE EXIT. SEC. 1017.3
 FBC.
  
 G) FLOOR CEILING FIRE RATED ASSEMBLY DRAWING IS NOT
 LEGIBLE. PROVIDE LEGIBLE DRAWING. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 4- NEED 1 HR FIRE RESISTANCE RATED CONSTRUCTION AT THE
 COMBUSTIBLE ROOF PROJECTION EXTENDING TO WITHIN 5 FEET
 OF THE PROPERTY LINE AS REQUIRED BY SEC. 705.2.3
 FBC-BUILDING. PROVIDE DETAIL AND SPECIFICATIONS FOR
 EAVE OVERHANG FIRE RATED ASSEMBLY.
  
 5- FBC-ACCESSIBILITY.
 A) PROVIDE COMPLIANCE WITH THE VERTICAL ACCESSIBILITY
 REQUIREMENTS FOR THE SECOND STORY OFFICE AS REQUIRED BY
 SEC. 201.1.1 FBC-ACCESSIBILITY. OR SHOW IN PLANS
 COMPLIANCE WITH ANY EXCEPTION.
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 ACCESSIBLE ROUTE SHOWING COMPLIANCE WITH SEC.
 206-FBC-ACCESSIBILITY.
 ACCESSIBLE ROUTE FROM PARKING TO THE BUILDING ENTRANCE
 (SEC. 402 AND SEC. 404 FBC-ACCESSIBILITY)
  
 C)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 STAIRWAY SHOWING COMPLIANCE WITH ALL THE REQUIREMENTS
 OF SEC. 504-FBC-ACCESSIBILITY.
 INCLUDE THE NOSING SPECIFICATIONS.
  
 D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 HANDRAILS SHOWING COMPLIANCE WITH ALL THE REQUIREMENTS
 OF SEC. 505-FBC-ACCESSIBILITY.
 HANDRAILS REQUIRED ON EACH SIDE OF STAIRWAY (REQ'D BY
 FBC ALSO).
  
 E) OFFICE ENTRANCE DOOR DOESN'T COMPLY WITH THE
 MANEUVERING REQUIREMENTS OF SEC. 404.2.4
 FBC-ACCESSIBILITY.
  
 F) PROVIDE COMPLETE DETAILS AND SPECIFICATION FOR
 ACCESSIBLE RESTROOMS SHOWING COMPLIANCE WITH ALL THE
 REQUIREMENTS OF CHAPTER 6- FBC-ACCESSIBILITY THAT
 APPLY.
 NOTE: 7'-0" MAY NOT COMPLY WITH THE OVERLAP ALLOWANCE
 OF SEC. 604.3.2 FBC-ACCESSIBILITY.
  
 6- LOCATION OF ATTIC ACCESS DOESN'T SEEM TO PROVIDE THE
 MIN. 30" CLEAR HEADROOM AS REQUIRED BY SEC. 1209.2 FBC.
 REVISE AS REQUIRED.
  
 7- SHEET A-1:
 A) WINDOWS AND DOORS DESIGN PRESSURES SHOWN ON
 WINDOW/DOORS SCHEDULES DON'T MATCH DESIGN PRESSURES
 SHOWN UNDER PRODUCT APPROVAL AFFIDAVIT ON SAME SHEET.
 ALSO, COORDINATE WITH DESIGN PRESSURES SHOWN ON SHEET
 S-2. REVISE AS REQUIRED TO MATCH. SEC. 1609.1 FBC.
  
 B) CLARIFY SIZE OF DOOR #2. SEE OPENING SIZE SHOWN ON
 FLOOR PLAN. SEC.107.2.1 CITY AMENDMENTS.
  
 8- RETAINING WALL DETAILS ON SHEET SP-1: CLARIFY
 VERTICAL REINFORCEMENT SIZE AND SPACING. SEC. 1609.1
 FBC.
  
 9- WINDER TREADS ARE NOT ALLOWED. SEC. 1011.5.3 FBC.
 REVISE STAIRS AS REQUIRED.
  
 10- SOIL TEST REPORT:
 A) NEED TO HAVE ENGINEER'S ORIGINAL SEAL AND SIGNATURE
 AS REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS. THIS IS NOT A DIGITAL
 SUBMITTAL.
  
 B) PROVIDE 2 COPIES. SEC. 107.1 CITY AMENDMENTS.
  
 C) THE PROPOSED CONSTRUCTION MATERIALS DON'T MATH
 PLANS. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 D) SOIL TEST FOOTING RECOMMENDATION AND PLANS DON'T
 MATCH. REVISE AS REQUIRED TO MATCH. IF FOOTING SIZE IS
 NOT REVISED, THEN DESIGNER OF RECORD TO PROVIDE
 JUSTIFICATION IN WRITING AS REQUIRED BY SEC. 107.2.1.2
 CITY AMENDMENTS.
  
 11- ENERGY CALCULATIONS:
 A) ARCHITECT OF RECORD TO CERTIFY (SIGNATURE AND
 LICENSE NUMBER) ON ENERGY FORM AS REQUIRED BY SEC.
 C103.1.1.1.2 FBC-ENERGY CONSERVATION.
  
 B) SHOW COMPLIANCE WITH THE BUILDING ENVELOPE
 REQUIREMENT SEC. C402.3. THERE IS A LOW SLOPE ROOF IN
 THIS BUILDING. REVISE INFORMATION ON PAGE 9 OF 22 AS
 REQUIRED. THIS IS NOT N/A.
  
 C) REVISE BUILDING ORIENTATION SHOWN ON PAGE 17 OF 22
 TO MATCH PLANS. NOTE: PLANS ARE DRAWN WITH NORTH ARROW
 POINTING SOUTH.
  
 D) REVISE WALL TYPES AND INSULATION INFORMATION SHOWN
 ON PAGE 17 OF 22 TO MATCH PLANS. ALSO, NEED TO PROVIDE
 INFORMATION FOR RAISED FLOOR ABOVE THE FIRST FLOOR
 UNCONDITIONED WAREHOUSE AREA. NOTE: COORDINATE WITH
 ARCHITECT.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE SHGC FACTOR
 SPECIFIED IN THE ENERGY CALCULATIONS WILL BE REQUIRED
 FOR INSPECTION.
  
  
 12- ARCHITECT TO COORDINATE INFORMATION ON PLANS WITH
 THE ENERGY CALCULATIONS TO AVOID CONFLICTS/DELAYS. SEC.
 C103.2 FBC-ENERGY CONSERVATION.
  
 13- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
 A) ENTRY DOORS. FLORIDA PRODUCT APPROVAL FL14237-R3
 SUBMITTED IS NOT APPROVED YET. IT' ONLY VALIDATED.
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 14- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 15- FLAT ROOF NOA 14-0627.05 SUBMITTED: CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 1609.1 FBC. NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED
 AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
  
 16- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 STAIRWAY CONSTRUCTION AS REQUIRED BY SEC. 1607.3 FBC.
  
 17- DESIGNER OF RECORD TO SPECIFY THE LIVE AND DEAD
 LOADS FOR SECOND FLOOR. SEC. 1606 AND SEC. 1607 FBC.
 NOTE: SEE SEC. 1607.11 FOR DISTRIBUTION OF FLOOR LOADS.
  
 18- TRUSS PACKAGE:
 A)TRUSS LAYOUT SHOWS A TOTAL FLOOR LOADING OF 70 PSF.
 THIS IS INCORRECT. IT DOESN'T ADD UP WITH ALL SPECIFIED
 LOADS. REVISE AS REQUIRED TO MATCH. SEC. 1606 AND 1607
 FBC.
  
 B) TRUSS ENGINEER TO PROVIDE ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 F.S. WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. COPIES ARE NOT
 ALLOWED.
  
 C) TRUSS PACKAGE COVER LETTER NEEDS TO PROVIDE THE
 INFORMATION OF THE PROFESSIONAL DESIGNER OF RECORD AS
 REQUIRED BY FAC 61G15-23.003.
  
 D) TRUSS LAYOUT SHOW THE TRUSS TO TRUSS STRUCTURAL
 CONNECTORS. TRUSS ENGINEER TO SIGN AND SEAL TRUSS
 LAYOUT AND PROVIDE HIS INFORMATION AS REQUIRED BY FAC
 61G15-23.001. OR PROVIDE COMPLETE STRUCTURAL
 CONNECTIONS ON EACH INDIVIDUAL TRUSS DRAWING.
  
 E)TRUSS ENGINEER TO PROVIDE ALL HIS INFORMATION ON ALL
 TRUSS DRAWINGS AS REQUIRED BY FAC 61G15-31.003 WHEN
 USING A COVER SHEET.
  
 19- DESIGNER OF RECORD TO REVIEW REVISED TRUSS PACKAGE,
 INCLUDING INDIVIDUAL TRUSSES BEFORE SUBMITTAL TO THIS
 OFFICE. SEC. 107.3.4.1 CITY AMENDMENTS.
  
 20- VALUE DECLARED I THE PERMIT APPLICATION IS TOO LOW.
 REVISE AS REQUIRED. SEC. 109.3 CITY AMENDMENTS.
  
 SEC. 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 21- WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
 NOTE: ENTER BUILDING INFORMATION ON FRONT SCREEN FIELDS
 WHEN PLANS ARE REVISED AND RESUBMITTED. JG.
  