Plan Review Notes
Plan Review Notes For Permit 18031354
Permit Number 18031354
Review Stop P
Sequence Number 1
Notes
Date Text
2018-04-09 11:49:491) SUBMIT TWO NEW CLEAR AND LEGIBLE COPIES OF THE
 MANUFACTURER'S SPECIFICATIONS FOR THE PENTAIR STARGUARD
 MAIN DRAIN. THE FLOW RATE ON THE SPCIFICATIONS CANNOT
 BE READ. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS IN ACCORDANCE
 WITH APSP 7-2013 SEC. 4.4.9.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW