Plan Review Notes
Plan Review Notes For Permit 18031344
Permit Number 18031344
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-04-03 12:40:21THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) IN AN EFFORT TO REDUCE FALSE ALARMS AND COMPLY WITH
 NFPA - IS THE SYSTEM PROGRAMABLE TO HAVE THE DUCT
 DETECTORS SEND A SUPERVISORY SIGNAL INSTEAD OF A FULL
 ALARM?
  
 IF SO, PLEASE EXECUTE AND TEST PER NFPA 72.
  
 NFPA 72
 23.8.5.4.6 SIGNAL INITIATION ? DUCT SMOKE DETECTORS.
 23.8.5.4.6.1 WHERE DUCT SMOKE DETECTORS ARE REQUIRED TO
 BE
 MONITORED AND A BUILDING FIRE ALARM SYSTEM IS
 INSTALLED, A DUCT
 DETECTOR ACTIVATION SIGNAL SHALL MEET THE REQUIREMENTS
 OF 21.7.4.
 21.7.4 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF HVAC
 SYSTEMS SHALL INITIATE A SUPERVISORY SIGNAL.
 21.7.4.1 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF
 HVAC
 SYSTEMS IN A FIRE ALARM SYSTEM WITHOUT A CONSTANTLY
 ATTENDED
 LOCATION OR SUPERVISING STATION SHALL BE PERMITTED TO
 INITIATE AN
 ALARM SIGNAL.
 21.7.4.2 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF
 HVAC
 SYSTEMS SHALL BE PERMITTED TO INITIATE AN ALARM SIGNAL
 WHERE
 REQUIRED BY OTHER GOVERNING LAWS, CODES, OR STANDARDS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  