| Plan Review Notes For Permit 18031344 |
| Permit Number |
18031344 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-04-03 12:40:21 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) IN AN EFFORT TO REDUCE FALSE ALARMS AND COMPLY WITH | | | NFPA - IS THE SYSTEM PROGRAMABLE TO HAVE THE DUCT | | | DETECTORS SEND A SUPERVISORY SIGNAL INSTEAD OF A FULL | | | ALARM? | | | | | | IF SO, PLEASE EXECUTE AND TEST PER NFPA 72. | | | | | | NFPA 72 | | | 23.8.5.4.6 SIGNAL INITIATION ? DUCT SMOKE DETECTORS. | | | 23.8.5.4.6.1 WHERE DUCT SMOKE DETECTORS ARE REQUIRED TO | | | BE | | | MONITORED AND A BUILDING FIRE ALARM SYSTEM IS | | | INSTALLED, A DUCT | | | DETECTOR ACTIVATION SIGNAL SHALL MEET THE REQUIREMENTS | | | OF 21.7.4. | | | 21.7.4 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF HVAC | | | SYSTEMS SHALL INITIATE A SUPERVISORY SIGNAL. | | | 21.7.4.1 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF | | | HVAC | | | SYSTEMS IN A FIRE ALARM SYSTEM WITHOUT A CONSTANTLY | | | ATTENDED | | | LOCATION OR SUPERVISING STATION SHALL BE PERMITTED TO | | | INITIATE AN | | | ALARM SIGNAL. | | | 21.7.4.2 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF | | | HVAC | | | SYSTEMS SHALL BE PERMITTED TO INITIATE AN ALARM SIGNAL | | | WHERE | | | REQUIRED BY OTHER GOVERNING LAWS, CODES, OR STANDARDS. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|