| Plan Review Notes For Permit 18031309 |
| Permit Number |
18031309 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-04-03 11:38:34 | PERMIT # 18031309 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FAILED COMMENTS: | | | | | | 1) SPOKE WITH KATJA WHYTE FROM ARCHITECTURE GROUP AND | | | WAS ADVISED THAT THIS PERMIT IS FOR THE WHITE BOX ONLY. | | | NO BUILD OUT WORK CONDUCTED. BUILD OUT PERMIT WILL BE | | | REQUIRED. | | | | | | 2) NOTE: PROVIDE DRAWING NOTE INDICATING, ?FIRE | | | PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING | | | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A | | | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN | | | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE | | | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST | | | BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING | | | (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE | | | FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? | | | | | | 3) NOTE: SEPARATE PLANS AND PERMITS ARE REQUIRED FOR | | | THE INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | | | 4) DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY | | | THE FIRE DEPARTMENT AFTER COMMENTS FROM ALL PLAN | | | REVIEWERS HAVE BEEN SATISFIED. | | | | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | [email protected] | | | |
|