Plan Review Notes
Plan Review Notes For Permit 18031309
Permit Number 18031309
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-04-03 11:38:34PERMIT # 18031309
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) SPOKE WITH KATJA WHYTE FROM ARCHITECTURE GROUP AND
 WAS ADVISED THAT THIS PERMIT IS FOR THE WHITE BOX ONLY.
 NO BUILD OUT WORK CONDUCTED. BUILD OUT PERMIT WILL BE
 REQUIRED.
  
 2) NOTE: PROVIDE DRAWING NOTE INDICATING, ?FIRE
 PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 3) NOTE: SEPARATE PLANS AND PERMITS ARE REQUIRED FOR
 THE INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 4) DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY
 THE FIRE DEPARTMENT AFTER COMMENTS FROM ALL PLAN
 REVIEWERS HAVE BEEN SATISFIED.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  