| 2018-04-02 09:43:31 | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE BUILDING PLANS EXAMINER |
| | |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33402 |
| | 561-805-6718 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE |
| | 2017 6TH EDITION |
| | |
| | FIRST REVIEW: |
| | |
| | 1) SHT. A100 - FIXTURE ELEVATIONS & ELEV. #01- THE |
| | TOILET PAPER DISPENSER SHALL BE LOCATED A MINIMUM OF 7 |
| | INCHES AND A MAXIMUM OF 9 INCHES IN FRONT OF THE WATER |
| | CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER AND |
| | THE OUTLET SHALL BE A MINIMUM OF 14 INCHES AND A |
| | MAXIMUM OF 19 INCHES ABOVE THE FINISH FLOOR. 2017 |
| | FBC-ACCESS. SEC. 604.9.6. |
| | |
| | 2) SHT. A100 - ELEVATIONS #01 & #02 - THE GRAB BARS |
| | SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE, |
| | NOT TO THE CENTER. 2017 FBC-ACCESS. SEC.609.4. |
| | |
| | 3) SHT. A100 - ELEV. #02 - THE OPERABLE PARTS OF THE |
| | HAND DRYER AND THE SANITARY NAPKIN DISPENSER SHALL BE |
| | LOCATED A MAXIMUM OF 48 INCHES ABOVE THE FINISH FLOOR |
| | PER 2017 FBC-ACCESS. SECS. 308 & 309. |
| | |
| | 4) SHOW THE CLEAR INSIDE DIMENSIONS ( LENGTH X WIDTH) |
| | OF THE NEW TOILET ROOM. IN ADDITION, SHOW THE CLEAR |
| | FLOOR SPACE DIMENSIONS FOR THE WATER CLOSET AND THE |
| | LAVATORY. COMPLY WITH 2017 FBC-ACCESS. SECS.604.3 AND |
| | 606.2. |
| | |
| | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 |
| | 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| | THE PERMIT PACKAGE. |
| | |
| | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| | |
| | |
| | |
| | |
| | PROVISO: |
| | |
| | |
| | 1. PROVIDE PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH |
| | ARE REGULATED BY FAC RULE 9N-3 REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD. SPECIFICALLY, |
| | STOREFRONT AND DOOR SUBMITTALS. FBC 107.3.4 |
| | |
| | FBC 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | |