Plan Review Notes
Plan Review Notes For Permit 18031221
Permit Number 18031221
Review Stop E
Sequence Number 3
Notes
Date Text
2018-10-12 09:05:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED. A CLASS L FUSE WILL ACCOMPLISH THIS
 REDUCTION IN FUSE SIZE. FYI, A FUSE REDUCER OF THIS
 SIZE DOES NOT EXIST.
 7. CORRECTED.
 8. PROVIDE ACCURATE LOAD BREAKDOWN. THE CURRENT
 EXPLANATION SHOWS THE NEW NORMAL LOAD TO BE 116 KW AND
 THE EMERGENCY LOAD TO BE 113 KW, BUT THE TOTAL PEAK
 DEMAND OF ONLY 113 KW. WHAT ARE THE LOADS FOR THE
 INDIVIDUAL SYSTEMS AND IS THE TOTAL CAPABLE OF BEING
 SUPPORTED BY THE NEW GENERATOR? PROVIDE CLARIFICATION.
 NEC 517.41(C) (AN ACCURATE LOAD CALCULATION, OR
 EQUIVALENT, WAS NOT PROVIDED. A FUTURE RECORDING IS NOT
 ACCEPTABLE. THIS INSTALLATION CANNOT BE APPROVED UNTIL
 ONE OF THE METHODS FOR LOAD DETERMINATION IS PROVIDED.
 IF NEC 220.87 IS INTENDED, A CERTIFIED RECORDING FOR 30
 DAYS WILL BE REQUIRED, OR DEMAND LOAD FOR A ONE YEAR
 PERIOD. ALL 3 ITEMS IN 220.87 ARE REQUIRED FOR APPROVAL
 UNDER THIS SECTION.)(3RD REVIEW: RESPONSE LETTER STATED
 THAT PROOF IN THE FORM OF AN EMAIL FROM FPL WAS TO BE
 PROVIDED. THIS WAS NOT INCLUDED IN THE PACKET. PROVIDE
 AS PREVIOUSLY REQUESTED.)
 9. PROVIDE DETAIL OF SEPARATION OF THE LIFE SAFETY
 BRANCH THE CRITICAL BRANCH. NEC 517.41(D) (BASED ON
 LOAD PROVIDED IN COMMENT 8, THIS MAY NOT BE NECESSARY
 IF LESS THAN 150 KW OF TOTAL LOAD.)(3RD REVIEW:
 CONFIRMATION OF LOAD NOT PROVIDED.)
 10. CORRECTED.
 11) WITH THE NEW DESIGN, PANEL MSB HAS BECOME A
 DOWNSTREAM PANEL AND IS REQUIRED TO HAVE THE GROUNDS
 AND NEUTRALS SEPARATED, AS WELL AS AN EGC INSTALLED IN
 THE EXISTING CONDUITS. THE GROUNDING ELECTRODE SYSTEM
 IS REQUIRED TO BE TIED IN AT THE MAIN SERVICE. PROVIDE
 CORRECTION. NEC 250.6, 250.24, 250.28, 250.30, 250.110,
 250.142(B)(3RD REVIEW: CORRECTION NOT PROVIDED ON PLAN
 FOR EXISTING WIRING TO MSB AND TO TRANSFER SWITCH THAT
 FEEDS PANEL E. BOTH OF THESE CONDUITS SHOW THE EXISTING
 FEED WITHOUT THE REQUIRED EQUIPMENT GROUNDING
 CONDUCTOR, SIZED PER CODE. PROVIDE CORRECTION AS
 PREVIOUSLY REQUESTED.)
  
 NEW COMMENTS:
 12. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE
 NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE NEXT
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 AGAIN FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW
 IS REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)
 FYI, FOR THIS PROJECT, THE ADDITIONAL PLAN REVIEW FEE
 WILL BE $3,550.00 BASED ON THE JOB VALUE OF $200,000.
 13. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  