| 2018-08-31 13:02:26 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. HOW WILL THE 500 AMP FUSE BE INSTALLED IN A 1600 AMP |
| | PIECE OF EQUIPMENT? PANEL MSB IS SHOWN WITH A 1600 AMP |
| | FUSE. OBVIOUSLY, THE FUSE SIZE WOULD BE DIFFERENT. |
| | PROVIDE CLARIFICATION. NEC110.3; FBC 107.2.1 (BY |
| | SEARCHING ONLINE, I WAS NOT ABLE TO FIND A REDUCER FROM |
| | 1600 AMPS TO 600 AMPS. PROVIDE MANUFACTURERS SPEC SHEET |
| | FOR THIS PRODUCT. AS A SIDE NOTE, WHY IS THIS BEING |
| | INSTALLED, AS THE CONDUCTORS AND SERVICE EQUIPMENT |
| | UPSTREAM ARE PROTECTED AT 600 AMP? IT SEEMS THE |
| | ORIGINAL FUSES COULD REMAIN IN PLACE, AS EVERYTHING |
| | AHEAD OF IT IS PROTECTED. NO CODE VIOLATION WITH |
| | CHANGING THE FUSE, BUT WE WILL NEED TO SEE A LISTED |
| | PRODUCT FOR THIS.) |
| | 7. CORRECTED. |
| | 8. PROVIDE ACCURATE LOAD BREAKDOWN. THE CURRENT |
| | EXPLANATION SHOWS THE NEW NORMAL LOAD TO BE 116 KW AND |
| | THE EMERGENCY LOAD TO BE 113 KW, BUT THE TOTAL PEAK |
| | DEMAND OF ONLY 113 KW. WHAT ARE THE LOADS FOR THE |
| | INDIVIDUAL SYSTEMS AND IS THE TOTAL CAPABLE OF BEING |
| | SUPPORTED BY THE NEW GENERATOR? PROVIDE CLARIFICATION. |
| | NEC 517.41(C) (AN ACCURATE LOAD CALCULATION, OR |
| | EQUIVALENT, WAS NOT PROVIDED. A FUTURE RECORDING IS NOT |
| | ACCEPTABLE. THIS INSTALLATION CANNOT BE APPROVED UNTIL |
| | ONE OF THE METHODS FOR LOAD DETERMINATION IS PROVIDED. |
| | IF NEC 220.87 IS INTENDED, A CERTIFIED RECORDING FOR 30 |
| | DAYS WILL BE REQUIRED, OR DEMAND LOAD FOR A ONE YEAR |
| | PERIOD. ALL 3 ITEMS IN 220.87 ARE REQUIRED FOR APPROVAL |
| | UNDER THIS SECTION.) |
| | 9. PROVIDE DETAIL OF SEPARATION OF THE LIFE SAFETY |
| | BRANCH THE CRITICAL BRANCH. NEC 517.41(D) (BASED ON |
| | LOAD PROVIDED IN COMMENT 8, THIS MAY NOT BE NECESSARY |
| | IF LESS THAN 150 KW OF TOTAL LOAD.) |
| | 10. CORRECTED. |
| | |
| | NEW COMMENT: |
| | |
| | 11) WITH THE NEW DESIGN, PANEL MSB HAS BECOME A |
| | DOWNSTREAM PANEL AND IS REQUIRED TO HAVE THE GROUNDS |
| | AND NEUTRALS SEPARATED, AS WELL AS AN EGC INSTALLED IN |
| | THE EXISTING CONDUITS. THE GROUNDING ELECTRODE SYSTEM |
| | IS REQUIRED TO BE TIED IN AT THE MAIN SERVICE. PROVIDE |
| | CORRECTION. NEC 250.6, 250.24, 250.28, 250.30, 250.110, |
| | 250.142(B) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |