2018-05-21 11:02:06 
 2ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18031215
 5/21/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE COMMENTS FROM THE 1ST REVIEW WERE NOT ADDRESSED.
 I HAVE REPRINTED THEM BELOW- PLEASE COMPLY.
  
  
 1ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18031215
 4/26/18
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 FIRELINE PIPING, VALVES, AND FITTINGS. CLARIFY HOW THE
 PIPING AND FITTINGS WILL RESTRAINED AGAINST MOVEMENT.
  
 2) ADVISORY: A SEPARATE PERMIT IS REQUIRED FOR THE
 BACKFLOW PREVENTER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  