Plan Review Notes
Plan Review Notes For Permit 18031215
Permit Number 18031215
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-03-29 11:37:39THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET 11 OF 16 & 12 OF 16 - THERE APPEARS TO BE ONE
 (1) FIRE LINE WATER SUPPLY LEADING TO EACH HIGH RISE'S
 FIRE PUMPS.
  
 PER NFPA 101 AND THE FLORIDA BUILDING CODE 2 SEPARATE
 WATER SUPPLIES ARE REQUIRED FOR EACH RIE PUMP.
  
 2014 NFPA 101 CHAPTER 11.
  
 11.1.6 MINIMUM CONSTRUCTION REQUIREMENTS. MINIMUM
 CONSTRUCTION REQUIREMENTS SHALL BE IN ACCORDANCE WITH
 THE APPLICABLE
 OCCUPANCY CHAPTER AND WITH THE FLORIDA BUILDING CODE.
  
 2014 FLORIDA BUIL;DING CODE:
  
 [F] 403.3.2 WATER SUPPLY TO REQUIRED FIRE PUMPS.
 REQUIRED FIRE PUMPS SHALL BE SUPPLIED BY CONNECTIONS TO
 NO FEWER THAN TWO WATER MAINS LOCATED IN DIFFERENT
 STREETS. SEPARATE SUPPLY PIPING SHALL BE PROVIDED
 BETWEEN EACH CONNECTION TO THE WATER MAIN AND THE
 PUMPS. EACH CONNECTION AND THE SUPPLY PIPING BETWEEN
 THE CONNECTION AND THE PUMPS SHALL BE SIZED TO SUPPLY
 THE FLOW AND PRESSURE REQUIRED FOR THE PUMPS TO
 OPERATE.
  
 EXCEPTION: TWO CONNECTIONS TO THE SAME MAIN SHALL BE
 PERMITTED PROVIDED THE MAIN IS VALVED SUCH THAT AN
 INTERRUPTION CAN BE ISOLATED SO THAT THE WATER SUPPLY
 WILL CONTINUE WITHOUT INTERRUPTION THROUGH NO FEWER
 THAN ONE OF THE CONNECTIONS.
  
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  