| Plan Review Notes For Permit 18031213 |
| Permit Number |
18031213 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-04-03 10:06:42 | 04/03/2018 1ST GAS REVIEW**DENIED** | | | | | | 1) YOUR VALUE OF TOTAL JOB SEEMS LOW. PER WPB AMEND TO | | | THE FBC 109.3 PROVIDE A SIGNED BONA FIDE CONTRACT | | | SHOWING TOTAL JOB VALUE.VALUE MUST INCLUDE THE COST OF | | | THE GAS COOK TOP ALONG WITH ALL MATERIAL, LABOR, | | | OVERHEAD, AND PROFIT. | | | | | | 2) PROVIDE COOK TOP MANUFACTURE INSTALLATION MANUAL. | | | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 | | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1 | | | | | | 3) CITY RECORDS SHOW AN EXISTING GAS POOL HEATER LISTED | | | AT 405,000 BTU THAT IS NOT SHOWING ON YOUR ISOMETRIC. | | | LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU | | | LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS | | | SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) | | | OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES | | | G2413.4 (1 ) THROUGH G2413.4 (21). | | | | | | 4) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE NEW | | | COOK TOP PER THE 2017 FBC-FUEL GAS CODE SEC.304.1, 2017 | | | FBC-RES. SEC. G 2407.1 | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|