| 2018-04-09 09:30:31 | 1ST REVIEW FBC-2014 MECHANICAL | | | REVISION #18031185 | | | MASTER #17110531 | | | 4/9/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE SCOPE OF THE MECHANICAL WORK FOR THE PROJECT HAS | | | INCREASED TO INCLUDE ALL NEW VAV'S, DUCTWORK, AND AIR | | | DEVICES IN THE SUITE. PLEASE PROVIDE THE INCREASED | | | VALUE OF THE PROJECT THAT INCLUDES LABOR, MATERIALS, | | | EQUIPMENT. DESIGN FEES, OVERHEAD AND PROFIT- SECTION | | | 109.3 WEST PALM BEACH AMENDMENTS TO THE FBC-17. | | | | | | 2) M2.1: IDENTIFY ALL ROOMS AND SPACES SHOWN IN THE NEW | | | MECHANICAL PLANS, AND PROVIDE MINIMUM VENTILATION | | | CALCULATIONS PER TABLE 403.3. | | | | | | 3) PROVIDE A REVISED REFLECTIVE CEILING PLAN. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|