| Plan Review Notes For Permit 18031167 |
| Permit Number |
18031167 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-03-26 16:40:01 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. THE FLAT DECK PRODUCT APPROVAL IS INCOMPLETE. | | | PROVIDE ALL PAGES OF THE INSTALLATION INSTRUCTIONS AND | | | THE EVALUATION REPORT THAT APPLY TO ALL ASSEMBLIES. | | | | | | 2. DESIGN PRESSURE FOR EXPOSURE C, ZONE 3 IS -95.7. THE | | | ASSEMBLY SELECTED HAS A DESIGN PRESSURE LIMITATION OF | | | -90. PLEASE ADDRESS. | | | | | | |
|