Plan Review Notes
Plan Review Notes For Permit 18031166
Permit Number 18031166
Review Stop P
Sequence Number 1
Notes
Date Text
2018-03-27 15:15:0403/27/2018 1ST PLUMBING REVIEW**DENIED**
  
 1) THE ADDRESS IS MISSING BOTH ON THE PERMIT
 APPLICATION AND PLAN. FBC 107.2.1
  
 2) PERSON DRAWNING PLAN MUST TAKE RESPONSIBILITY BE
 PRINT NAME AND SIGNING. FBC 107.2.1
  
 3) THE VALUE OF JOB SEEMS LOW. PROVIDE BONA FIDE SIGNED
 CONTRACT PER WPB AMEND TO THE FBC 109.3
  
 4) YOUR PLAN IS SHOWING 2 WATER METERS AND 3 BACKFLOWS.
 PLEASE CLARIFY WHICH ARE NEW AND WHICH ARE EXISTING AS
 WELL AS WHO INSTALLED THEM. PLEASE INCLUDE MODEL AND
 SERIAL NUMBER FOR EACH AND VERIFY THAT THEY ARE
 LEAD-FREE AS NO BACKFLOW PERMITS ARE SHOWN IN THE
 SYSTEM FOR THIS PROPERTY. FBC 107.2.1
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER