Plan Review Notes
Plan Review Notes For Permit 18031052
Permit Number 18031052
Review Stop M
Sequence Number 4
Notes
Date Text
2018-12-21 13:02:203RD REVIEW FBC-2010 MECHANICAL
 PERMIT #18031052
 12/21/18
  
 PLAN REVIEW RESULTS: DENIED. (PLAN REVIEW I N PROGRESS,
 DO NOT PRINT).
  
 1) THE SPECS FOR THE DOWN DRAFT SYSTEMS DO NOT INDICATE
 SYSTEMS ARE DESIGNED FOR RECIRCULATION, AND BASED ON
 THE 1000 CFM MAXIMUM EXHAUST RATINGS, MAKEUP AIR WILL
 BE REQUIRED PER SECTION 505.2 FBC M.
  
 2) SHEETS M2.1 AND A4.6: THE PLANS DO NOT SHOW THE
 KITCHEN EXHAUST SYSTEMS ABOVE THE COOKTOPS ARE IN
 COMPLIANCE WITH SEVERAL ITEMS LISTED UNDER SECTION
 505.3 FBC M- SEE BELOW.
  
 505.3 COMMON EXHAUST SYSTEMS FOR DOMESTIC KITCHENS
 LOCATED IN MULTISTORY STRUCTURES.
  
 WHERE A COMMON MULTISTORY DUCT SYSTEM IS DESIGNED AND
 INSTALLED TO CONVEY EXHAUST FROM MULTIPLE DOMESTIC
 KITCHEN EXHAUST SYSTEMS, THE CONSTRUCTION OF THE SYSTEM
 SHALL BE IN ACCORDANCE WITH ALL OF THE FOLLOWING:
  
 5.THE EXHAUST FAN MOTOR DESIGN SHALL BE IN ACCORDANCE
 WITH SECTION 503.2. PLEASE REVIEW SECTION 503.2 AND
 PROVIDE MANUFACTURER'S SPECIFICATIONS FOR EF-C WITH
 INFORMATION INDICATING COMPLIANCE.
  
 6. THE EXHAUST FAN MOTOR SHALL BE LOCATED OUTSIDE OF
 THE AIRSTREAM.
  
 7.THE EXHAUST FAN SHALL RUN CONTINUOUSLY, AND SHALL BE
 CONNECTED TO A STANDBY POWER SOURCE.
  
 8. EXHAUST FAN OPERATION SHALL BE MONITORED IN AN
 APPROVED LOCATION AND SHALL INITIATE AN AUDIBLE OR
 VISUAL SIGNAL WHEN THE FAN IS NOT IN OPERATION.
  
 3) SECTIONS 917.1 & 017.2 REQUIRE UL LISTING AND
 LABELING FOR THE MIELE COOKING APPLIANCES, HOWEVER I'M
 NOT SEEING ANY EVIDENCE OF UL LISTING IN THE SUBMITTED
 SPEC SHEETS.
  
 4) AS PREVIOUSLY NOTED, THE DRYER BOOSTER FAN SPECS DO
 NOT INDICATE THE FAN IS LISTED AND LABELED FOR USE WITH
 A CLOTHES DRYER- SECTION 504.6.4.1 FBC M.
  
 5) M2.1: PLEASE MODIFY NOTE #26 TO INDICATE THE DRYER
 BOOSTER FAN WILL ALSO BE ENCLOSED IN THE PLENUM RATED
 EXHAUST CHASE AND PROVIDE CONSTRUCTION DETAILS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  