| 2018-12-21 13:02:20 | 3RD REVIEW FBC-2010 MECHANICAL |
| | PERMIT #18031052 |
| | 12/21/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. (PLAN REVIEW I N PROGRESS, |
| | DO NOT PRINT). |
| | |
| | 1) THE SPECS FOR THE DOWN DRAFT SYSTEMS DO NOT INDICATE |
| | SYSTEMS ARE DESIGNED FOR RECIRCULATION, AND BASED ON |
| | THE 1000 CFM MAXIMUM EXHAUST RATINGS, MAKEUP AIR WILL |
| | BE REQUIRED PER SECTION 505.2 FBC M. |
| | |
| | 2) SHEETS M2.1 AND A4.6: THE PLANS DO NOT SHOW THE |
| | KITCHEN EXHAUST SYSTEMS ABOVE THE COOKTOPS ARE IN |
| | COMPLIANCE WITH SEVERAL ITEMS LISTED UNDER SECTION |
| | 505.3 FBC M- SEE BELOW. |
| | |
| | 505.3 COMMON EXHAUST SYSTEMS FOR DOMESTIC KITCHENS |
| | LOCATED IN MULTISTORY STRUCTURES. |
| | |
| | WHERE A COMMON MULTISTORY DUCT SYSTEM IS DESIGNED AND |
| | INSTALLED TO CONVEY EXHAUST FROM MULTIPLE DOMESTIC |
| | KITCHEN EXHAUST SYSTEMS, THE CONSTRUCTION OF THE SYSTEM |
| | SHALL BE IN ACCORDANCE WITH ALL OF THE FOLLOWING: |
| | |
| | 5.THE EXHAUST FAN MOTOR DESIGN SHALL BE IN ACCORDANCE |
| | WITH SECTION 503.2. PLEASE REVIEW SECTION 503.2 AND |
| | PROVIDE MANUFACTURER'S SPECIFICATIONS FOR EF-C WITH |
| | INFORMATION INDICATING COMPLIANCE. |
| | |
| | 6. THE EXHAUST FAN MOTOR SHALL BE LOCATED OUTSIDE OF |
| | THE AIRSTREAM. |
| | |
| | 7.THE EXHAUST FAN SHALL RUN CONTINUOUSLY, AND SHALL BE |
| | CONNECTED TO A STANDBY POWER SOURCE. |
| | |
| | 8. EXHAUST FAN OPERATION SHALL BE MONITORED IN AN |
| | APPROVED LOCATION AND SHALL INITIATE AN AUDIBLE OR |
| | VISUAL SIGNAL WHEN THE FAN IS NOT IN OPERATION. |
| | |
| | 3) SECTIONS 917.1 & 017.2 REQUIRE UL LISTING AND |
| | LABELING FOR THE MIELE COOKING APPLIANCES, HOWEVER I'M |
| | NOT SEEING ANY EVIDENCE OF UL LISTING IN THE SUBMITTED |
| | SPEC SHEETS. |
| | |
| | 4) AS PREVIOUSLY NOTED, THE DRYER BOOSTER FAN SPECS DO |
| | NOT INDICATE THE FAN IS LISTED AND LABELED FOR USE WITH |
| | A CLOTHES DRYER- SECTION 504.6.4.1 FBC M. |
| | |
| | 5) M2.1: PLEASE MODIFY NOTE #26 TO INDICATE THE DRYER |
| | BOOSTER FAN WILL ALSO BE ENCLOSED IN THE PLENUM RATED |
| | EXHAUST CHASE AND PROVIDE CONSTRUCTION DETAILS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | |