| 2018-11-06 17:37:33 | 2ND REVIEW FBC-2010 MECHANICAL |
| | PERMIT #18031052 |
| | 11/6/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE AC CALCULATION PRINTOUT IS INDICATING MIAMI AS |
| | THE PROJECT LOCATION. PLEASE PROVIDE CALCULATIONS USING |
| | THE CORRECT LOCATION, AND INCLUDE THE ADDRESS AND UNIT |
| | NUMBER ON THE CALCULATION PRINTOUT. |
| | |
| | 2) M2.1: SMOKE DETECTORS ARE REQUIRED IN BOTH THE |
| | SUPPLY AND THE RETURN SYSTEMS OF THE HP'S- SECTION |
| | 606.2 FBC M. |
| | |
| | 3) M2.1: PROVIDE THE RETURN OPENING DIMENSIONS AT EACH |
| | HP CLOSET- SECTION 601.4 FBC M. |
| | |
| | 4) M2.1: THERE IS INSUFFICENT INFORMATION AND DETAILS |
| | ON THE PLAN TO SHOW COMPLIANCE FOR THE REQUIRED KITCHEN |
| | EXHAUST SYSTEMS: |
| | |
| | A) PLEASE PROVIDE ENLARGED KITCHEN EXHAUST DETAILS ON |
| | THE PLAN SHOWING THE COOKTOP DOWNDRAFT EXHAUST DUCT |
| | RUNS AND TERMINATION LOCATIONS. CLARIFY IF TWO SYSTEMS |
| | WILL BE INSTALLED- ONE FOR THE GAS-FIRED COOKTOP AND |
| | ONE FOR THE ELECTRIC COOKTOP. SPECS HAVE BEEN SUBMITTED |
| | FOR EACH HOWEVER THE PLAN APPEARS TO SHOW ONLY ONE |
| | COOKTOP. |
| | |
| | B) THE COMB-OVEN, SPEED OVEN, AND CONVECTION OVEN EACH |
| | REQUIRE AN EXHAUST VENTILATION SYSTEM HOWEVER NO SPECS |
| | FOR THE VENTS HAVE BEEN SUBMITTED AND NO DETAILS HAVE |
| | BEEN PROVIDED ON THE PLAN. |
| | |
| | C) PLEASE REFER TO TABLE 403.3 WHICH REQUIRES AN |
| | EXHAUST VENTILATION RATE OF 25 CFMS PER SF. FOR |
| | CONTINUOUS VENTILATION, AND 100 CFMS PER SF. FOR |
| | INTERMITTENT VENTILATION. |
| | |
| | 5) THE DRYER BOOSTER FAN SPECS DO NOT INDICATE THE FAN |
| | IS LISTED AND LABELED FOR USE WITH A CLOTHES DRYER- |
| | SECTION 504.6.4.1 FBC M |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |