| 2018-09-05 17:04:27 | 1ST REVIEW FBC-2010 MECHANICAL |
| | PERMIT #18031052 |
| | 9/5/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | PLEASE NOTE THAT ALL APARTMENT BUILDOUTS WILL BE |
| | DESIGNED UNDER THE 2010 FLORIDA BUILDING CODES UNTIL |
| | WHICH TIME THE ENTIRE BUILDING RECEIVES A CERTIFICATE |
| | OF OCCUPANCY. |
| | |
| | 1) PLEASE REPLACE THE ENERGYGAUGE 2017 COMPLIANCE |
| | SUBMITTAL WITH THE 2010 VERSION AND PROVIDE PIPING |
| | SYSTEM COMPLIANCE DATA THAT IS MISSING FROM THE FORM. |
| | |
| | 2) M2.1: SHOW THE LOCATION OF THE O/A DUCT THAT IS |
| | SUPPLYING THE UNITS VIA THE RETURN AIR PLENUM, |
| | |
| | 3) M2.1: DUE TO THE FACT THAT THE AC CLOSETS ARE |
| | SHARING A COMMON PLENUM SMOKE DETECTORS SHALL BE |
| | PROVIDED IN THE RETUN AIR PLENUM IN ACCORDANCE WITH |
| | SECTION 606.2.2 FBC M. |
| | |
| | 4) M2.1: REGARDING THE INTUMESCENT PAINT ON THE AC |
| | CLOSET DOORS, IT HAS BEEN DETERMINED THAT THE ENGINEER |
| | OF RECORD SHALL BE RESPONSIBLE FOR INSPECTING AND |
| | CERTIFYING THE APPLICATION PROCESS. PLACE A NOTE ON THE |
| | PLAN ACCORDINGLY. |
| | |
| | 5) M2.1: THE RESPONSE NARRATIVE FROM THE JOHNSON GROUP |
| | IS REFERENCING SHEET AXX FOR THE DRYER ENCLOSURE |
| | DETAIL. I WAS NOT ABLE TO LOCATE THE SHEET OR DETAIL. |
| | |
| | 6) M2.1: THE RESPONSE NARRATIVE FROM THE JOHNSON GROUP |
| | IS REFERENCING A DIMENSIONED, SEGMENTED DRAWING OF THE |
| | DRYER EXHAUST DUCT WHICH I WAS UNABLE TO LOCATE. PLEASE |
| | PROVIDE THE DRAWING. |
| | |
| | 7) M2.1 : CLARIFY THE NEED FOR THE DRYER EXHAUST |
| | BOOSTER FAN. PER THE EQUIVALENT LENGTH TABLE, THE 120 |
| | FT. RUN DOES NOT EXCEED THE 125 FT. MAXIMUM RUN ALLOWED |
| | BY THE MANUFACTURER. IN ADDITION, PLEASE CONTACT FIRE |
| | CHIEF PETER LEDUC FOR PERMISSION TO INSTALL THE BOOSTER |
| | FAN. IF PERMITTED, AN ACCESS PANEL WILL BE REQUIRED FOR |
| | SERVICE AND REPLACEMENT OF THE FAN- SECTION 306.1. |
| | |
| | 8) M2.1: THE COMBUSTION AIR CALCULATION TABLE LISTS THE |
| | KITCHEN AT 3860 SQ. FT. WHICH CLEARLY FROM THE DRAWINGS |
| | IT IS NOT. PLEASE PROVIDE AN ACCURATE CALCULATION. |
| | |
| | 9) THE REQUESTED PRODUCT DATA SHEETS FOR THE GAS FIRED |
| | APPLIANCES AND DOWN DRAFT EXHAUST SYSTEM WERE NOT |
| | PROVIDED. PLEASE NOTE THAT AN EXHAUST HOOD MAY BE |
| | REQUIRED FOR THE OVENS PER SECTION 507.2.2 FBC M. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | |