| 2018-05-16 11:29:14 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THIS BUILDING IS REQUIRED TO COMPLY WITH THE FAIR | | | HOUSING ACT PLEASE INDICATE ON THE PLAN WHICH DESIGN | | | DOCUMENT THAT WAS USED IN DESIGNING THIS UNIT TO COMPLY | | | WITH FHA . PER WPB AMEND TO FBC 107.2.1 | | | | | | 2. PLEASE INDICATE ON THE PLAN WHICH BATHROOM OR | | | BATHROOMS ARE USABLE AND WHICH DESIGN SPECIFICATION A | | | OR B THAT WAS USED TO COMPLY WITH FHA REQUIREMENTS # 6 | | | +7 | | | | | | 3. PLEASE PROVIDE A ENLARGED FLOOR PLAN SHOWING THE | | | REQUIRED CLEAR FLOOR SPACE FHA REQUIREMENTS # 7 | | | | | | 4. PROVIDE ELEVATION DETAILS SHOWING MOUNTING HEIGHTS | | | FOR THE GRAB BAR BACKING PER FHA REQUIREMENT # 6 | | | | | | 5. SHT. P-3.2 THE DETAIL FOR THE KITCHEN AND PANTRY | | | SHOWS A STACK THAT IS NOT LABELED OR SIZED IT HAS A | | | CLEAN OUT BUT NO FIXTURE ITS LOCATED NEXT TO THE SK | | | PLEASE LABEL AND SIZE. PER WPB AMEND TO FBC 107.2.1 | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|