2018-05-16 11:29:141ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THIS BUILDING IS REQUIRED TO COMPLY WITH THE FAIR
 HOUSING ACT PLEASE INDICATE ON THE PLAN WHICH DESIGN
 DOCUMENT THAT WAS USED IN DESIGNING THIS UNIT TO COMPLY
 WITH FHA . PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE INDICATE ON THE PLAN WHICH BATHROOM OR
 BATHROOMS ARE USABLE AND WHICH DESIGN SPECIFICATION A
 OR B THAT WAS USED TO COMPLY WITH FHA REQUIREMENTS # 6
 +7
  
 3. PLEASE PROVIDE A ENLARGED FLOOR PLAN SHOWING THE
 REQUIRED CLEAR FLOOR SPACE FHA REQUIREMENTS # 7
  
 4. PROVIDE ELEVATION DETAILS SHOWING MOUNTING HEIGHTS
 FOR THE GRAB BAR BACKING PER FHA REQUIREMENT # 6
  
 5. SHT. P-3.2 THE DETAIL FOR THE KITCHEN AND PANTRY
 SHOWS A STACK THAT IS NOT LABELED OR SIZED IT HAS A
 CLEAN OUT BUT NO FIXTURE ITS LOCATED NEXT TO THE SK
 PLEASE LABEL AND SIZE. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  