| 2018-04-11 12:02:17 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) COVER SHEET - THE ADDRESS IN THE TITLE BLOCK |
| | INDICATES 1112 S FLAGLER. THE ADDRESS OF THE BUILDING |
| | IS 1100 S FAGLER. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY. |
| | |
| | |
| | |
| | 2) THERE IS SMOKEGAURD SMOKE CURTAIN INDICATED AT THE |
| | ELEVATOR LOBBY. |
| | |
| | THIS OPENING ALSO FUNCTION A AN EXIT/EXIT ACCESS TO |
| | THIS RESIDENCE. HOW WILL THIS OPENING/CURTAIN FUNCTION |
| | AS AN EXIT/EXIT ACCESS IN THE EVENT IT ACTIVATES AND IS |
| | IN THE DOWN POSITION? |
| | |
| | ADDITIONALLY, THE BUREAU HAS TESTED PREVIOUS PROPOSED |
| | SIMILAR CURTAINS THAT FAIL TO STAY SECURED DUE TO |
| | PRESSURIZATION OF OTHER LIFE SAFETY SYSTEMS. HAS THE |
| | PRESSURIZATION OF THE ELEVATOR BEEN CONSIDERED WITH THE |
| | EOR OF THIS BUILDING. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS |
| | |
| | |
| | |
| | 3) SHEET F O.1 - THE FIRE SPRINKLER DRAWINGS APPEAR TO |
| | HAVE AN ENGINEER STAMP AND/OR SEAL. THERE CAN BE ONLY |
| | ONE ENGINEEER OF RECORD FOR THE SPRINKLER SYSTEM. |
| | |
| | DOES THIS STAMPED SET CONFLICT WITH THE ORIGINAL EOR |
| | STAMP AND DOES THE EOR APPROVE OF THIS DESIGN. |
| | |
| | PLEASE REVIEW, CORRECT OR JUSTIFY WITH DETAILS. |
| | |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |