| 2018-05-04 10:18:38 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | PAGE E-1.1 |
| | |
| | NOTE #4 UPDATE CODE EDITIONS |
| | |
| | NOTE #62 UPDATE NOTE TO REFLECT NEC CODE 2014 ARC |
| | FAULTS IN KITCHEN AND LAUNDRY AREAS |
| | ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH |
| | CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT KITCHENS, |
| | LAUNDRY ROOMS, |
| | FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, |
| | LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, |
| | CLOSETS, HALLWAYS, |
| | OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI PROTECTION. |
| | NEC 210.12; FBC RE3902.16 |
| | |
| | PAGE E-2.1 |
| | |
| | OUTLET SPACING SEEMS TO BE DEFICIENT IN MOST ROOMS |
| | E3901.2.1 SPACING. RECEPTACLES SHALL BE INSTALLED SO |
| | THAT NO POINT MEASURED HORIZONTALLY ALONG THE FLOOR |
| | LINE OF ANY |
| | WALL SPACE IS MORE THAN 6 FEET (1829 MM), FROM A |
| | RECEPTACLE OUTLET. [210.52(A)(1)] |
| | E3901.2.2 WALL SPACE. |
| | AS USED IN THIS SECTION, A WALL SPACE SHALL INCLUDE THE |
| | FOLLOWING: [210.52(A)(2)] |
| | 1. 1.ANY SPACE THAT IS 2 FEET (610 MM) OR MORE IN |
| | WIDTH, INCLUDING SPACE MEASURED AROUND CORNERS, AND |
| | THAT IS |
| | UNBROKEN ALONG THE FLOOR LINE BY DOORWAYS AND SIMILAR |
| | OPENINGS, FIREPLACES, AND FIXED CABINETS. |
| | 2. 2.THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR |
| | WALLS, EXCLUDING SLIDING PANELS. |
| | 3. 3.THE SPACE CREATED BY FIXED ROOM DIVIDERS SUCH AS |
| | RAILINGS AND FREESTANDING BAR-TYPE COUNTERS |
| | |
| | |
| | OUTLETS MISSING ON BALCONY |
| | E3901.7 OUTDOOR OUTLETS. |
| | NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY |
| | ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 |
| | FEET, 6 INCHES |
| | (1981 MM) ABOVE GRADE, SHALL BE INSTALLED OUTDOORS AT |
| | THE FRONT AND BACK OF EACH DWELLING UNIT HAVING DIRECT |
| | ACCESS TO |
| | GRADE LEVEL. BALCONIES, DECKS, AND PORCHES THAT ARE |
| | ACCESSIBLE FROM INSIDE OF THE DWELLING UNIT SHALL HAVE |
| | AT LEAST ONE |
| | RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE |
| | BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE |
| | LOCATED NOT MORE |
| | THAN 6 FEET, 6 INCHES (1981 MM) ABOVE THE BALCONY, |
| | DECK, OR PORCH SURFACE. [210.52(E)] |
| | |
| | KITCHEN AND LAUNDRY AREAS NEED ARC FAULT PROTECTION |
| | ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH |
| | CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT KITCHENS, |
| | LAUNDRY ROOMS, |
| | FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, |
| | LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, |
| | CLOSETS, HALLWAYS, |
| | OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI PROTECTION. |
| | NEC 210.12; FBC RE3902.16 |
| | |
| | PAGE E-4.1 |
| | |
| | PANEL SCHEDULES NEED TO REFLECT NEW AFCL/GFCI |
| | PROVISIONS |
| | |
| | NEED TO SUBMIT FAULT CURRENT CALCULATIONS |
| | |
| | NEED TO SUBMIT A LOAD CALCULATION |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, |
| | IT IS HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING |
| | EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED |
| | PAGES INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6713 |