2018-05-04 10:18:38FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-1.1
  
 NOTE #4 UPDATE CODE EDITIONS
  
 NOTE #62 UPDATE NOTE TO REFLECT NEC CODE 2014 ARC
 FAULTS IN KITCHEN AND LAUNDRY AREAS
 ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT KITCHENS,
 LAUNDRY ROOMS,
 FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS,
 LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS,
 CLOSETS, HALLWAYS,
 OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI PROTECTION.
 NEC 210.12; FBC RE3902.16
  
 PAGE E-2.1
  
 OUTLET SPACING SEEMS TO BE DEFICIENT IN MOST ROOMS
 E3901.2.1 SPACING. RECEPTACLES SHALL BE INSTALLED SO
 THAT NO POINT MEASURED HORIZONTALLY ALONG THE FLOOR
 LINE OF ANY
 WALL SPACE IS MORE THAN 6 FEET (1829 MM), FROM A
 RECEPTACLE OUTLET. [210.52(A)(1)]
 E3901.2.2 WALL SPACE.
 AS USED IN THIS SECTION, A WALL SPACE SHALL INCLUDE THE
 FOLLOWING: [210.52(A)(2)]
 1. 1.ANY SPACE THAT IS 2 FEET (610 MM) OR MORE IN
 WIDTH, INCLUDING SPACE MEASURED AROUND CORNERS, AND
 THAT IS
 UNBROKEN ALONG THE FLOOR LINE BY DOORWAYS AND SIMILAR
 OPENINGS, FIREPLACES, AND FIXED CABINETS.
 2. 2.THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR
 WALLS, EXCLUDING SLIDING PANELS.
 3. 3.THE SPACE CREATED BY FIXED ROOM DIVIDERS SUCH AS
 RAILINGS AND FREESTANDING BAR-TYPE COUNTERS
  
  
 OUTLETS MISSING ON BALCONY
 E3901.7 OUTDOOR OUTLETS.
 NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY
 ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6
 FEET, 6 INCHES
 (1981 MM) ABOVE GRADE, SHALL BE INSTALLED OUTDOORS AT
 THE FRONT AND BACK OF EACH DWELLING UNIT HAVING DIRECT
 ACCESS TO
 GRADE LEVEL. BALCONIES, DECKS, AND PORCHES THAT ARE
 ACCESSIBLE FROM INSIDE OF THE DWELLING UNIT SHALL HAVE
 AT LEAST ONE
 RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE
 BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE
 LOCATED NOT MORE
 THAN 6 FEET, 6 INCHES (1981 MM) ABOVE THE BALCONY,
 DECK, OR PORCH SURFACE. [210.52(E)]
  
 KITCHEN AND LAUNDRY AREAS NEED ARC FAULT PROTECTION
 ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT KITCHENS,
 LAUNDRY ROOMS,
 FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS,
 LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS,
 CLOSETS, HALLWAYS,
 OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI PROTECTION.
 NEC 210.12; FBC RE3902.16
  
 PAGE E-4.1
  
 PANEL SCHEDULES NEED TO REFLECT NEW AFCL/GFCI
 PROVISIONS
  
 NEED TO SUBMIT FAULT CURRENT CALCULATIONS
  
 NEED TO SUBMIT A LOAD CALCULATION
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING,
 IT IS HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING
 EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED
 PAGES INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER
 561-805-6713
 [email protected]
  