| Plan Review Notes For Permit 18031038 |
| Permit Number |
18031038 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-04-06 16:54:40 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE LEGIBLE PLANS, SIGNED AND SEALED BY A | | | FLORIDA LICENSED PROFESSIONAL ENGINEER. | | | 2. FIRE ESCAPE SHALL COMPLY WITH THE PROVISIONS OF FBC | | | EXISTING BUILDING, SECTION 405. | | | 3. PROVIDE SHOP DRAWINGS FOR PROPOSED FIRE ESCAPE. | | | 4. IF FIELD WELDS ARE UTILIZED, PROVIDE WELDER | | | CERTIFICATIONS. | | | 5. CURRENT CODE IN EFFECT IS THE 2017 FBC 6TH EDITION. | | | | | | FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS | | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON | | | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. | | | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, | | | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO | | | RECORDS MANAGEMENT. | | | | | | PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE, | | | DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE | | | 61G15-23.001. | | | | | | | | | | | | |
|