| Plan Review Notes For Permit 18031029 |
| Permit Number |
18031029 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-04-24 20:01:25 | 04/24/2018 2ND GAS REVIEW**DENIED** | | | | | | 1) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 | | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. THE | | | SPECIFICATION SUPPLIED FOR THE POOL HEATER AND THE | | | STOVE TOP DOES NOT CONTAIN ANY APPROVAL VERIFICATION. | | | YOU DID NOT SUPPLY ANY INFORMATION ON THE OUTSIDE BBQ | | | GRILL. PROVIDE THE FULL INSTALLATION MANUAL FOR THE | | | TANKLESS WATER HEATERS. | | | | | | 2) IS THE OUTSIDE BBQ GRILL LOCATED UNDER ANY TYPE OF | | | ROOF COVERING? A HOOD VENT MAY BE REQUIRED. FBC 107.2.1 | | | | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|