| 2018-03-29 07:28:23 | 03/29/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS RES. SEC. |
| | G2408.1. |
| | 2. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION FBC FUEL GAS RES. SEC. G2421.1. |
| | 3. NEED A SHUTOFF VALVE AND HARD CAP FOR FUTURE |
| | GENERATOR SHOWN ON GAS ISOMERIC P-1.02 APPLIANCE |
| | SHUTOFF 2017 FBC FUEL GAS RES. SEC. G2420.5, APPLIANCE |
| | CONNECTION 2017 FBC FUEL GAS RES. SEC. G 2415.15. |
| | 4. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE |
| | DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| | OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| | ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| | SYSTEM 2017 FBC FUEL GAS RES. SEC. G2413.3 |
| | 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR, WHERE IS |
| | COMBUSTION AIR PROVIDED BY THE BUILDING?S MECHANICAL |
| | VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE |
| | SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE |
| | REQUIRED VENTILATION AIR. 2017 FBC FUEL GAS RES. SEC. |
| | G2407.1 AND G2439.4. |
| | 6. PE PIPE IN GROUND IT?S NOT ALLOWED, THE INSTALLATION |
| | OF PLASTIC PIPE SHALL COMPLY WITH SECTIONS G2415.17.1 |
| | THROUGH G2415.17.3. |
| | 7. SHOW ALL REQUIRED HUT OFF VALVES, REGULATORS AND |
| | DISTANCES, VALVES TO BE LOCATED IN THE SAME ROOM, A |
| | LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR FBC FUEL GAS RES. SEC. |
| | G2420.4. |
| | 8. ON YOUR ENERGY EFFICIENCY FORM R405-2017 IT SHOW THE |
| | WATER HEATER AS BEING ELECTRICAL AND A PLAN SHOW 2 GAS |
| | TANKLESS THEY MUST COMPLY WITH THE E.F .067 AS REQUIRED |
| | BY THE TABLE R402A. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |