| Plan Review Notes For Permit 18031026 |
| Permit Number |
18031026 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-04-02 11:03:23 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | REVISION IS DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PRODUCT APPROVALS (FL22513-R1 & FL22633-R2) FOR | | | THE EXTERIOR DOORS THAT WERE SUBMITTED ARE NOT | | | COMPLETE. THE REQUIRED EVALUATION REPORT AND | | | INSTALLATION INSTRUCTIONS ARE MISSING. FAC 61G20-3.001 | | | | | | 2) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR | | | THE PROJECT. FBC 107.3.4 | | | | | | 3) THE REVISED PLAN SHEETS A6.0 THAT WERE SUBMITTED ARE | | | REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OF | | | RECORD, ALFONSO HERNANDEZ. FS 481 & FAC 471 | | | | | | |
|