| Plan Review Notes For Permit 18031011 |
| Permit Number |
18031011 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-04-12 14:54:51 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PANEL SCHEDULES SHOW NEW CIRCUITS BEING ADDED, BUT | | | NO PLAN IS PROVIDED DETAILING LOCATION AND QUANTITY OF | | | LIGHT FIXTURES OR THE DETAILS OF FEATURE PUMP. PROVIDE | | | ELECTRICAL PLAN FOR REVIEW SHOWING ALL WORK ON THIS | | | PERMIT. FBC 107.2.1, 107.3.5 | | | 2. PROVIDE EXTERIOR LIGHTING CONTROLS AS SPECIFIED IN | | | THE FBC ENERGY CONSERVATION. FBC EC C405.2.5 | | | 3. PROVIDE DETAILS OF COMPLIANCE WITH FBC EC C404.9. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|