2018-05-25 14:37:2505/25/18 TALKED TO ROBERT BROWN. WE NEED TO ENFORCE THE
 BARRIER HEIGHT OF 8 FEET.
  
  
 BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- A) CONSTRUCTION BARRIER CAN NOT BE LESS THAN 8'-0"
 HIGH AS REQUIRED BY SEC. 3306.5 FBC. REVISE INFORMATION
 SUBMITTED AS REQUIRED.
  
 B) THE REQUIRED 8'-0" HIGH CONSTRUCTION BARRIER TO BE
 DESIGNED TO MEET THE WIND LOADS OF CHAPTER 16 AS
 REQUIRED BY SEC. 3306.6 FBC. CLEARLY PROVIDE POST
 SPACING AND POST ANCHORING SPECIFICATIONS.
  
 2- A COVERED WALKWAY IS ALSO REQUIRED BY TABLE 3306.1
 FBC AND SEC. 3306.7 FBC. PROVIDE COMPLETE INFORMATION.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  