| Plan Review Notes For Permit 18031000 |
| Permit Number |
18031000 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-06-01 17:59:47 | 06/01/2018 3RD GAS REVIEW**DENIED** WITH COMMENTS NOTE | | | - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME | | | AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED | | | UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | A SEPARATE GAS APPLICATION AND INSPECTION IS REQUIRED | | | FOR THIS MASTER PERMIT. | | | | | | 1. PLEASE COMBINE YOUR TWO ISOMETRIC DRAWINGS INTO ONE | | | AND PUT THE TABLE NUMBER YOU ARE USING. WPB AMENDMENTS | | | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. | | | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 | | | FBC FUEL GAS SEC. 304.1, 614.5 (CLOTHES DRYERS) OR 2017 | | | FBC FUEL GAS RES. SEC. G2407.1 AND G2439.4 (CLOTHES | | | DRYERS). | | | 3. INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER A | | | ROOF. WPB AMEND. TO FBC SEC. 107.2.1 | | | 4. SUBMIT MANUFACTURES SPECIFICATIONS FOR THE GRILL. | | | FGC SEC.305.1, FBC-RES. SEC.G2408.1. | | | | | | SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS MAY | | | RESULT IN NEW PLAN REVIEW COMMENTS. WHEN RESUBMITTING, | | | IT IS HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING | | | EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE OR VOID THE PREVIOUSLY REVIEWED | | | SHEETS. | | | |
|