Plan Review Notes
Plan Review Notes For Permit 18031000
Permit Number 18031000
Review Stop G
Sequence Number 3
Notes
Date Text
2018-06-01 17:59:4706/01/2018 3RD GAS REVIEW**DENIED** WITH COMMENTS NOTE
 - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 A SEPARATE GAS APPLICATION AND INSPECTION IS REQUIRED
 FOR THIS MASTER PERMIT.
  
 1. PLEASE COMBINE YOUR TWO ISOMETRIC DRAWINGS INTO ONE
 AND PUT THE TABLE NUMBER YOU ARE USING. WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC FUEL GAS SEC. 304.1, 614.5 (CLOTHES DRYERS) OR 2017
 FBC FUEL GAS RES. SEC. G2407.1 AND G2439.4 (CLOTHES
 DRYERS).
 3. INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER A
 ROOF. WPB AMEND. TO FBC SEC. 107.2.1
 4. SUBMIT MANUFACTURES SPECIFICATIONS FOR THE GRILL.
 FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS. WHEN RESUBMITTING,
 IT IS HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING
 EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE OR VOID THE PREVIOUSLY REVIEWED
 SHEETS.
  