| 2018-06-07 09:28:28 | RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017). |
| | |
| | 1- A) IT LOOKS LIKE WINDOW IN BEDROOM #2 DOESN'T COMPLY |
| | WITH ALL THE EGRESS REQUIREMENTS OF SEC. R210 |
| | FBC-RESIDENTIAL. DESIGN PROFESSIONAL TO PROVIDE SIZE |
| | AND TYPE OF WINDOW SHOWING COMPLIANCE. |
| | |
| | B) DESIGN PROFESSIONAL TO SPECIFY TYPE AND SIZE OF ALL |
| | NEW WINDOWS SHOWN ON PLANS. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | A) NEW WINDOWS AS SHOWN ON PLANS. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | B) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK |
| | SIZE OF MULLION TO BE USED TO VERIFY COMPLIANCE WITH |
| | THE DESIGN PRESSURES. COORDINATE WITH ITEM #1 ABOVE. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | 3- DESIGN PROFESSIONAL OF RECORD TO REVIEW AND APPROVE |
| | IN WRITING (NOT SIGNING AND SEALING) ALL PRODUCT |
| | APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS |
| | |
| | 4- PROVIDE STRUCTURAL BUCK DETAILS FOR NEW WINDOWS. |
| | SEC. R609.7.2.1 FBC-RESIDENTIAL. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | |