2018-04-09 15:40:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS
 481.229; WPB FBC 107.2.1, 107.3.5.1.2
 2. PROVIDE ELECTRICAL PLAN WITH A MINIMUM 1/8 INCH
 SCALE. "BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8
 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER
 ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO
 ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE
 SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY,
 OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
 ELECTRONIC MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE
 REQUIREMENTS OF FLORIDA STATUTES." WPB FBC 107.2.1.3
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE
 E3706.2, E3902
 4. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 RE R314.3, R315.1; WPB FBC 107.2.1
 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved