| 2018-06-06 16:33:12 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 600.6(A)(1) DISCONNECT ALL POWER BEFORE IT ENTERS THE |
| | SIGN. DISCOONECT IN SIGHT OF SIGN. |
| | |
| | 600. 6 DISCONNECTS (A) LOCATION. |
| | (1) AT POINT OF ENTRY TO A SIGN ENCLOSURE. THE |
| | DISCONNECT |
| | SHALL BE LOCATED AT THE POINT THE FEEDER CIRCUIT OR |
| | BRANCH CIRCUIT(S) |
| | SUPPLYING A SIGN OR OUTLINE LIGHTING SYSTEM ENTERS A |
| | SIGN ENCLOSURE |
| | OR A POLE IN ACCORDANCE WITH 600.5(C)(3) AND SHALL |
| | DISCONNECT |
| | ALL WIRING WHERE IT ENTERS THE ENCLOSURE OF THE SIGN OR |
| | POLE |
| | |
| | |
| | VALUE FOR THE SIGN TO LOW FOR A SIGN THIS SIZE. CITY |
| | WILL ASSIGN A VALUE OF $5000 TO THE SIGN. |
| | |
| | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, |
| | PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE |
| | WORK, |
| | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION |
| | REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF |
| | NATIONAL CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL- |
| | SWIFT, MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE |
| | SET BY THE BUILDING OFFICIAL |
| | |