| 2018-05-31 14:19:18 | 2ND REVIEW COMMENTS: |
| | |
| | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | 1) THE PROPOSED INSTALLATION SHALL COMPLY WITH THE |
| | REQUIREMENTS OF NFPA? 37 |
| | |
| | STANDARD FOR THE INSTALLATION AND USE OF STATIONARY |
| | COMBUSTION ENGINES AND GAS TURBINES, 2015 EDITION |
| | |
| | PLEASE ENSURE COMPLIANCE. |
| | |
| | |
| | 2) NO DIMENSION IS INDICATED FOR THE WIDTH FROM THE |
| | EXISTING BUILDING, |
| | |
| | PER NFPA 37 |
| | |
| | 4.1.4 ENGINES LOCATED OUTDOORS. ENGINES, AND THEIR |
| | WEATHERPROOF |
| | HOUSINGS, IF PROVIDED, THAT ARE INSTALLED OUTDOORS |
| | SHALL |
| | BE LOCATED AT LEAST 1.5 M (5 FT) FROM OPENINGS IN WALLS |
| | AND AT |
| | LEAST 1.5 M (5 FT) FROM STRUCTURES HAVING COMBUSTIBLE |
| | WALLS. A |
| | MINIMUM SEPARATION SHALL NOT BE REQUIRED WHERE EITHER |
| | OF THE |
| | FOLLOWING CONDITIONS EXIST: |
| | (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 1.5 |
| | M (5 FT) |
| | FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE RATING |
| | OF |
| | AT LEAST 1 HOUR. |
| | (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF |
| | NONCOMBUSTIBLE |
| | MATERIALS AND IT HAS BEEN DEMONSTRATED THAT A FIRE |
| | WITHIN THE ENCLOSURE WILL NOT IGNITE COMBUSTIBLE |
| | MATERIALS |
| | OUTSIDE THE ENCLOSURE. |
| | |
| | PLEASE ENSURE COMPLIANT SEPARATION AND/OR FIRE |
| | RESISTNACE RATING. |
| | |
| | 3) THERE IS NO INDICATION OF COMPLAINCE WITH NFPA 54 |
| | |
| | PER NFPA 37 |
| | |
| | 5.1* GAS PIPING. |
| | 5.1.1 GAS PIPING SHALL BE INSTALLED IN ACCORDANCE WITH |
| | THE |
| | FOLLOWING METHODS: |
| | (1) ALL FUEL GAS SYSTEMS AT SERVICE PRESSURES EQUAL TO |
| | OR LESS |
| | THAN A GAUGE PRESSURE OF 860 KPA (GAUGE PRESSURE OF |
| | 125 PSI) SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 54, |
| | NATIONAL FUEL GAS CODE. |
| | (2) ALL FUEL GAS SYSTEMS AT SERVICE PRESSURES IN EXCESS |
| | OF A |
| | GAUGE PRESSURE OF 860 KPA (GAUGE PRESSURE OF 125 PSI), |
| | OTHER THAN LP-GAS SYSTEMS, SHALL BE INSTALLED IN |
| | ACCORDANCE |
| | WITH ANSI/ASME B31.3, PROCESS PIPING. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |