Plan Review Notes
Plan Review Notes For Permit 18030944
Permit Number 18030944
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2018-05-31 14:19:182ND REVIEW COMMENTS:
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE PROPOSED INSTALLATION SHALL COMPLY WITH THE
 REQUIREMENTS OF NFPA? 37
  
 STANDARD FOR THE INSTALLATION AND USE OF STATIONARY
 COMBUSTION ENGINES AND GAS TURBINES, 2015 EDITION
  
 PLEASE ENSURE COMPLIANCE.
  
  
 2) NO DIMENSION IS INDICATED FOR THE WIDTH FROM THE
 EXISTING BUILDING,
  
 PER NFPA 37
  
 4.1.4 ENGINES LOCATED OUTDOORS. ENGINES, AND THEIR
 WEATHERPROOF
 HOUSINGS, IF PROVIDED, THAT ARE INSTALLED OUTDOORS
 SHALL
 BE LOCATED AT LEAST 1.5 M (5 FT) FROM OPENINGS IN WALLS
 AND AT
 LEAST 1.5 M (5 FT) FROM STRUCTURES HAVING COMBUSTIBLE
 WALLS. A
 MINIMUM SEPARATION SHALL NOT BE REQUIRED WHERE EITHER
 OF THE
 FOLLOWING CONDITIONS EXIST:
 (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 1.5
 M (5 FT)
 FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE RATING
 OF
 AT LEAST 1 HOUR.
 (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NONCOMBUSTIBLE
 MATERIALS AND IT HAS BEEN DEMONSTRATED THAT A FIRE
 WITHIN THE ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS
 OUTSIDE THE ENCLOSURE.
  
 PLEASE ENSURE COMPLIANT SEPARATION AND/OR FIRE
 RESISTNACE RATING.
  
 3) THERE IS NO INDICATION OF COMPLAINCE WITH NFPA 54
  
 PER NFPA 37
  
 5.1* GAS PIPING.
 5.1.1 GAS PIPING SHALL BE INSTALLED IN ACCORDANCE WITH
 THE
 FOLLOWING METHODS:
 (1) ALL FUEL GAS SYSTEMS AT SERVICE PRESSURES EQUAL TO
 OR LESS
 THAN A GAUGE PRESSURE OF 860 KPA (GAUGE PRESSURE OF
 125 PSI) SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 54,
 NATIONAL FUEL GAS CODE.
 (2) ALL FUEL GAS SYSTEMS AT SERVICE PRESSURES IN EXCESS
 OF A
 GAUGE PRESSURE OF 860 KPA (GAUGE PRESSURE OF 125 PSI),
 OTHER THAN LP-GAS SYSTEMS, SHALL BE INSTALLED IN
 ACCORDANCE
 WITH ANSI/ASME B31.3, PROCESS PIPING.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]