Plan Review Notes
Plan Review Notes For Permit 18030944
Permit Number 18030944
Review Stop E
Sequence Number 1
Notes
Date Text
2018-04-16 16:02:34FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 VALUE FOR WORK SHOWN IS LOW.
  
 PERMIT STATES A 30KW GENERATOR AND PLANS CALL FOR A
 35KW
  
 NEED TO SUBMIT A VOLTAGE DROP CALCULATION ON THE
 FEEDERS FROM THE GENERATOR.
  
 NEED TO SUBMIT A FAULT CURRENT CALCULATION FOR THE
 EXISTING SERVICE EQUIPMENT TO BE USED IN THIS
 INSTALLATION.
  
 LOAD CALCULATION FOR GENERATOR.
  
 WIRE SIZES SHOWN COPPER OR ALUMINUM?
  
 HOW DO YOU GET TO THE ROOF, STAIRWELL?????
2018-04-14 08:28:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 6TH
 EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 6TH EDITION, PART
 VIII ELECTRICAL
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 [email protected]
 561-657-1653