Plan Review Notes
Plan Review Notes For Permit 18030836
Permit Number 18030836
Review Stop M
Sequence Number 3
Notes
Date Text
2018-08-28 14:50:00PASS PROVISO
  
 PERMIT #18030836
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-101.00: THE PLAN DOES NOT CLEARLY SHOW HOW
 O/A IS BEING PROVIDED TO HP-G (IN CLOSET BY FOOD
 PANTRY), AND HP-B AND HOW THAT AIR IS AUTOMATICALLY
 CONTROLLED.
  
 2) SHEET A-101, A-501, & M-101.00: NOTE #5 ON THE
 MECHANICAL PLAN CALLS OUT INTUMESCENT PAINT ON A
 FIRE-RATED FLUSH DOOR AT THE HP-G CLOSET (CLOSET BY
 CORE CORRIDOR). IT IS NOT CLEAR WHY THIS FIRE-RATED
 DOOR WOULD NEED INTUMESCENT PAINT. IS THE DOOR MADE OF
 COMBUSTIBLE MATERIALS AND NOT PLENUM RATED? PLEASE
 CLARIFY.
  
 3) M-101.00: IN REGARD TO NOTE #5 WE REQUIRE THAT THE
 ENGINEER OF RECORD CONDUCT THE INSPECTIONS OF THE
 INTUMESCENT PAINT APPLICATION ON THE AC CLOSET DOORS
  
 4) M-101.00: DUE TO THE FACT THAT THE HP-B CLOSET
 APPEARS TO BE PART OF THE RETURN AIR PLENUM, A SMOKE
 DETECTOR IS REQUIRED IN ALL THREE CLOSETS IN COMPLIANCE
 WITH SECTION 606.2.2 FBC-10 MECH.
  
 5) THE SUBMITTED CUT SHEET FOR THE WOLF COOKTOP DOES
 INDICATE THE APPLIANCE HAS BEEN TESTED TO THE
 APPROPRIATE ANSI STANDARD LISTED UNDER SECTION 623.1
 FBC-10 FUEL GAS AT ROUGH INSPECTION.
  