| Plan Review Notes For Permit 18030836 |
| Permit Number |
18030836 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-08-28 14:50:00 | PASS PROVISO | | | | | | PERMIT #18030836 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-101.00: THE PLAN DOES NOT CLEARLY SHOW HOW | | | O/A IS BEING PROVIDED TO HP-G (IN CLOSET BY FOOD | | | PANTRY), AND HP-B AND HOW THAT AIR IS AUTOMATICALLY | | | CONTROLLED. | | | | | | 2) SHEET A-101, A-501, & M-101.00: NOTE #5 ON THE | | | MECHANICAL PLAN CALLS OUT INTUMESCENT PAINT ON A | | | FIRE-RATED FLUSH DOOR AT THE HP-G CLOSET (CLOSET BY | | | CORE CORRIDOR). IT IS NOT CLEAR WHY THIS FIRE-RATED | | | DOOR WOULD NEED INTUMESCENT PAINT. IS THE DOOR MADE OF | | | COMBUSTIBLE MATERIALS AND NOT PLENUM RATED? PLEASE | | | CLARIFY. | | | | | | 3) M-101.00: IN REGARD TO NOTE #5 WE REQUIRE THAT THE | | | ENGINEER OF RECORD CONDUCT THE INSPECTIONS OF THE | | | INTUMESCENT PAINT APPLICATION ON THE AC CLOSET DOORS | | | | | | 4) M-101.00: DUE TO THE FACT THAT THE HP-B CLOSET | | | APPEARS TO BE PART OF THE RETURN AIR PLENUM, A SMOKE | | | DETECTOR IS REQUIRED IN ALL THREE CLOSETS IN COMPLIANCE | | | WITH SECTION 606.2.2 FBC-10 MECH. | | | | | | 5) THE SUBMITTED CUT SHEET FOR THE WOLF COOKTOP DOES | | | INDICATE THE APPLIANCE HAS BEEN TESTED TO THE | | | APPROPRIATE ANSI STANDARD LISTED UNDER SECTION 623.1 | | | FBC-10 FUEL GAS AT ROUGH INSPECTION. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|