| 2018-08-21 14:36:25 | 1ST REVIEW FBC-2010 MECHANICAL, ENERGY CONSERVATION |
| | CODE |
| | PERMIT #18030836 |
| | 8/21/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-101.00: THE PLAN DOES NOT CLEARLY SHOW HOW |
| | O/A IS BEING PROVIDED TO HP-G (IN CLOSET BY FOOD |
| | PANTRY), AND HP-B AND HOW THAT AIR IS AUTOMATICALLY |
| | CONTROLLED. |
| | |
| | 2) SHEET A-101, A-501, & M-101.00: NOTE #5 ON THE |
| | MECHANICAL PLAN CALLS OUT INTUMESCENT PAINT ON A |
| | FIRE-RATED FLUSH DOOR AT THE HP-G CLOSET (CLOSET BY |
| | CORE CORRIDOR). IT IS NOT CLEAR WHY THIS FIRE-RATED |
| | DOOR WOULD NEED INTUMESCENT PAINT. IS THE DOOR MADE OF |
| | COMBUSTIBLE MATERIALS AND NOT PLENUM RATED? PLEASE |
| | CLARIFY. |
| | |
| | 3) M-101.00: IN REGARD TO NOTE #5, THE CITY OF WEST |
| | PALM BEACH REQUIRES THAT THE ENGINEER OF RECORD CONDUCT |
| | THE INSPECTIONS OF THE INTUMESCENT PAINT APPLICATION ON |
| | THE AC CLOSET DOORS, AND PROVIDE THE DEPARTMENT WITH A |
| | SIGNED SEALED LETTER CERTIFYING THE APPLICATION |
| | PROCEDURE WAS COMPLETED ACCORDING TO THE MANUFACTURER'S |
| | SPECIFICATIONS. PLEASE PLACE A NOTE ON THE PLAN TO THAT |
| | EFFECT- SECTION 107.2.1 WPB AMENDMENTS TO THE FBC. |
| | |
| | 4) M-101.00: DUE TO THE FACT THAT THE HP-B CLOSET |
| | APPEARS TO BE PART OF THE RETURN AIR PLENUM, A SMOKE |
| | DETECTOR IS REQUIRED IN THE CLOSET IN COMPLIANCE WITH |
| | SECTION 606.2.2 FBC-10 MECH. |
| | |
| | 5) M-102.00: PLEASE LABEL THE SUBDUCT DETAILS AS EITHER |
| | DRYER, TOILET, OR KITCHEN EXHAUST. |
| | |
| | 6) THE SUBMITTED CUT SHEET FOR THE WOLF COOKTOP DOES |
| | INDICATE THE APPLIANCE HAS BEEN TESTED TO THE |
| | APPROPRIATE ANSI STANDARD LISTED UNDER SECTION 623.1 |
| | FBC-10 FUEL GAS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |