| 2018-07-02 11:35:23 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. IT HAS COME TO MY ATTENTION THAT THE PLANS FOR THIS |
| | UNIT INCLUDE CHANGES TO WHAT WE CONSIDER "COMMON AREA". |
| | THIS CHANGE IS NOT CLOUDED, SO WAS NOT REVIEWED BY THE |
| | PREVIOUS REVIEWER. |
| | |
| | A LOCK HAS BEEN ADDED TO DOOR CN01. IT IS NOT CLEAR HOW |
| | EXITING FOR THE ADJACENT UNIT IS AFFECTED; THIS SHOULD |
| | BE A REVISION TO THE BASE BUILDING PLAN AND INCLUDE A |
| | REVISED LIFE SAFETY PLAN IF THIS WAS PREVIOUSLY SHOWN |
| | AS AN EXIT FOR THE ADJACENT UNIT. |
| | |
| | WHEN RESUBMITTING, ADDRESS THIS COMMENT AS WELL AS |
| | COMMENTS FROM PREVIOUS REVIEW. FOR YOUR CONVENIENCE, |
| | THEY ARE INCLUDED BELOW. |
| | |
| | |
| | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE BUILDING PLANS EXAMINER |
| | |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33402 |
| | |
| | 561-805-6718 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE |
| | 2017 6TH EDITION |
| | |
| | 1. PERMIT APPLICATIONS SUBMITTED AFTER 12/31/17 SHALL |
| | BE DESIGNED UNDER THE FLORIDA BUILDING CODE 2017 6TH |
| | EDITION INCLUDING MECHANICAL, PLUMBING, ENERGY |
| | CONSERVATION AND ACCESSIBILITY. CHANGE ALL CODE |
| | REFERENCES THROUGHOUT THE PLANS TO REFLECT THIS UPDATE. |
| | |
| | 2. PROVIDE ELEVATIONS FOR KITCHEN AND BATHROOM COUNTERS |
| | SO THAT WE CAN CHECK FOR COMPLIANCE WITH FAIR HOUSING. |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. FLOOR SOUND UNDERLAYMENT |
| | |
| | 1) SUFFOLK CONSTRUCTION TO CONDUCT SITE TESTING FOR |
| | COMPLIANCE WITH THE 2010 FBC-B SECTIONS: |
| | |
| | FBC-B 2010 1207.2 AIR-BORNE SOUND. |
| | FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | |
| | THE SOUND TESTS WILL BE CONDUCTED ON A 10 INCH CONCRETE |
| | SLAB UNDER THE MAIN PERMIT (15111020) AND SUBMITTED AS |
| | SOON AS RESULTS ARE PRINTED AND REVIEWED BY THE |
| | DESIGNER OF RECORD. |
| | NOTE: SITE TESTING FOR FLOOR INSULATION WILL REQUIRE |
| | THE APPLICANT TO REQUEST (IN WRITING) UNDER THE 2010 W. |
| | P. B. ADMINISTRATIVE CODE SECTION 104.11 ALTERNATE |
| | MATERIALS, DESIGN AND METHODS OF CONSTRUCTION FOR THE |
| | SOUND UNDERLAYMENT. THE LETTER SHOULD BE MADE OUT TO |
| | THE BUILDING OFFICIAL ROBERT BROWN. |
| | |
| | SHEET: FINISHES. UNIT: |
| | |
| | FLOOR FINISHES. BLDG TYPE: TYPE I/ TYPE II FLOOR |
| | INSULATION (FBC-B 2010) |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 10 INCH CONCRETE FLOOR ASSEMBLY AS PER PLAN OR PROVIDE |
| | ONSITE TESTING TO THE LISTED BELOW ASTM STANDARDS: |
| | |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 4. SHOW FLOOR TRANSITION DETAIL FROM CONDO FLOOR TO |
| | LOBBY FLOOR. |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. IN THE STEAM ROOM WINDOWS ARE SHOWN ON THE EXTERIOR |
| | WALL OPENING INWARD. HAS THE EXTERIOR ENVELOPE OF THE |
| | BUILDING CHANGED. PLEASE PROVIDE A DETAIL FOR THIS |
| | AREA. THERE IS NOT A WINDOW SHOWN ON THE SCHEDULE FOR |
| | THIS ROOM. |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 6. PROVIDE DETAILS FOR GLASS ENCLOSURES USED AT STEAM |
| | ROOM, SHOWERS AND TOILET ROOMS. SHOW IF THESE GLASS |
| | PANELS WILL BE SUPPORTED ON ALL SIDES. |
| | |
| | FBC 2403.2 GLASS SUPPORTS. |
| | WHERE ONE OR MORE SIDES OF ANY PANE OF GLASS ARE NOT |
| | FIRMLY SUPPORTED, OR ARE SUBJECTED TO UNUSUAL LOAD |
| | CONDITIONS, DETAILED CONSTRUCTION DOCUMENTS, DETAILED |
| | SHOP DRAWINGS AND ANALYSIS OR TEST DATA ENSURING SAFE |
| | PERFORMANCE FOR THE SPECIFIC INSTALLATION SHALL BE |
| | PREPARED BY A REGISTERED DESIGN PROFESSIONAL. |
| | |
| | 7. ARCHITECTURAL PAGES NOT DIGITALLY SIGNED. |
| | |
| | ARCHITECT DIGITAL SIGNING & SEALING PLANS. 61G1-16.005 |
| | PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR |
| | ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS. |
| | |
| | (1) INFORMATION STORED IN ELECTRONIC FILES REPRESENTING |
| | PLANS, SPECIFICATIONS, PLATS, REPORTS, OR OTHER |
| | DOCUMENTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF |
| | CHAPTER 481, F.S., SHALL BE SIGNED, DATED AND SEALED BY |
| | THE ARCHITECT OR INTERIOR DESIGNER IN RESPONSIBLE |
| | CHARGE. |
| | (A) A SCANNED IMAGE OF AN ORIGINAL SIGNATURE SHALL NOT |
| | BE USED IN LIEU OF A DIGITAL OR ELECTRONIC SIGNATURE. |
| | (B) THE DATE THAT THE ELECTRONIC SIGNATURE FILE WAS |
| | CREATED OR THE DIGITAL SIGNATURE WAS PLACED INTO THE |
| | DOCUMENT MUST APPEAR ON THE DOCUMENT IN THE SAME MANNER |
| | AS DATE IS REQUIRED TO BE APPLIED WHEN A LICENSEE USES |
| | THE MANUAL SEALING PROCEDURE SET OUT IN RULE |
| | 61G1-16.003, F.A.C. |
| | (2) AN ARCHITECT OR INTERIOR DESIGNER UTILIZING A |
| | DIGITAL SIGNATURE TO SEAL CONSTRUCTION DOCUMENTS SHALL |
| | ASSURE THAT THE DIGITAL SIGNATURE IS: |
| | (A) UNIQUE TO THE PERSON USING IT; |
| | (B) CAPABLE OF VERIFICATION; |
| | (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; AND |
| | (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE |
| | ELECTRONIC SIGNATURE IS INVALIDATED IF ANY DATA IN THE |
| | DOCUMENT ARE CHANGED. |
| | (3) EACH ELECTRONICALLY SIGNED FILE SHALL HAVE AN |
| | AUTHENTICATION CODE DEFINED AS A MESSAGE DIGEST |
| | DESCRIBED IN FEDERAL INFORMATION PROCESSING STANDARD |
| | PUBLICATION 180-4 ?SECURE HASH STANDARD,? MARCH 2012, |
| | WHICH IS HEREBY ADOPTED AND INCORPORATED BY REFERENCE |
| | BY THE BOARD AND CAN BE OBTAINED FROM HTTP://WWW.FLRULE |
| | S.ORG/GATEWAY/REFERENCE.ASP?NO=REF-01340 OR THE |
| | INTERNET WEBSITE: HTTP://CSRC.NIST.GOV/PUBLICATIONS/FIP |
| | S/FIPS180-4/FIPS-180-4.PDF. |
| | |
| | |
| | |
| | |
| | |
| | |
| | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 |
| | 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | |
| | |
| | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| | |