2018-04-07 16:06:371ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A601 SHOWER PAN DETAIL THE WATER PROF MEMBRANE
 SHALL PITCH TO THE DRAIN THE MEMBRANE SHOWN ON THE
 CONCRETE SLAB DOES NOT APPEAR TO COMPLY WITH FBC PL
 417.5.2
  
 2. PLEASE SPECIFY ON PLAN THE MANUFACTURE OF THE WATER
 PROF MEMBRANE AND PROVIDE SPECIFICATIONS AND
 INSTALLATION GUIDE. PER WPB AMEND TO FBC 107.2.1
  
 3. PLEASE PROVIDE ELEVATION DETAILS FOR GRAB BAR
 BACKING AND THE VANITY'S IN HER BATHROOM AS IT IS
 DESIGNATED A SPEC B BATHROOM FOR THE FHA REQUIREMENTS.
 PER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENTS #6 AND
 #7
  
 4. THE TUB IS MISSING ON THE SANITARY ISOMETRIC IN HER
 MASTER BATHROOM. PER WPB AMEND TO FBC 107.2.1
  
 5. PLEASE PROVIDE MANUFACTURE SPECIFICATION AND INSTALL
 MANUAL FOR THE STEAM GENERATOR. PER WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  