| 2018-04-09 15:46:17 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18030836 |
| | 4/9/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-101.00: THE 30"X10" DUCT IS NOT PERMITTED TO |
| | PENETRATE INTO THE INTERIOR STAIRWELL ENCLOSURE- |
| | SECTION 1023.5 FBC-17 BUILDING. |
| | |
| | 2) M-101.00: PROVIDE A INSTALLATION DETAIL FROM THE |
| | FIRE/SMOKE DAMPER MANUFACTURER SHOWING HOW THE DAMPERS |
| | ARE TO BE INSTALLED IN THE DUCT RUNS AS SHOWN IN THE |
| | APARTMENT CORE. |
| | |
| | 3) M-101.00: EXHAUST SYSTEMS ARE REQUIRED IN THE MASTER |
| | BATHS- TABLE 403.1.1. |
| | |
| | 4) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | HEAT PUMPS- SECTION C403.2.1 FBC-17 ENERGY |
| | CONSERVATION. |
| | |
| | 5) PROVIDE AN ENERGY COMPLIANCE REPORT- SECTION C101.5 |
| | |
| | 6) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE |
| | SPACE IN ACCORDANCE WITH TABLE 403.1.1, AND INDICATE |
| | HOW THE OUTDOOR AIR FLOW WILL BE AUTOMATICALLY |
| | CONTROLLED- SEE SECTION C403.2.4.3 FBC-17 ENERGY |
| | CONSERVATION. CLARIFY HOW O/A IS BEING SUPPLIED TO THE |
| | HEAT PUMPS. |
| | |
| | 7) M1.01.00 SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY |
| | TRUNKS OF HP-G- SECTION 606.2.1. |
| | |
| | 8) M1.01.00 & A-4: NON-COMBUSTIBLE DOORS ARE REQUIRED |
| | FOR THE AC CLOSETS IN COMPLIANCE WITH SECTION 602.2 |
| | FBC-17 MECHANICAL, AND C403.2.9.2 FBC-17 ENERGY |
| | CONSERVATION. |
| | |
| | 9) M1.01.00: PROVIDE A SECTION CUT OF THE COVE RETURNS |
| | THAT SHOWS THE DIMENSIONS OF THE OPENING, AND WHAT |
| | CONSTRUCTION MATERIALS WILL BE USED- SECTION 602.2 |
| | |
| | 10) M.101.00: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| | THE GAS RANGE, EXHAUST HOOD, AND EXHAUST DUCT. PROVIDE |
| | A DETAIL SHOWING THE CONNECTION OF THE EXHAUST DUCT |
| | INTO THE SHAFT. |
| | |
| | 11) M1.01.00: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| | THE DRYER, AND PROVIDE A DETAIL SHOWING THE CONNECTION |
| | OF THE EXHAUST DUCT INTO THE SHAFT. |
| | |
| | 12) M-102.00: PLEASE INDICATE WHICH OF THE SUBDUCT |
| | DETAILS APPLIES TO THE DRYER EXHAUST, THE TOILET |
| | EXHAUST, AND THE RANGE EXHAUST. |
| | |
| | 13) M-102.03: PROVIDE MANUFACTURER'S SPECIFICATIONS FOR |
| | THE DUCT WRAP WITH SHOP DRAWING APPROVAL STAMP BY THE |
| | EOR. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |