2018-04-09 15:46:171ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18030836
 4/9/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-101.00: THE 30"X10" DUCT IS NOT PERMITTED TO
 PENETRATE INTO THE INTERIOR STAIRWELL ENCLOSURE-
 SECTION 1023.5 FBC-17 BUILDING.
  
 2) M-101.00: PROVIDE A INSTALLATION DETAIL FROM THE
 FIRE/SMOKE DAMPER MANUFACTURER SHOWING HOW THE DAMPERS
 ARE TO BE INSTALLED IN THE DUCT RUNS AS SHOWN IN THE
 APARTMENT CORE.
  
 3) M-101.00: EXHAUST SYSTEMS ARE REQUIRED IN THE MASTER
 BATHS- TABLE 403.1.1.
  
 4) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 HEAT PUMPS- SECTION C403.2.1 FBC-17 ENERGY
 CONSERVATION.
  
 5) PROVIDE AN ENERGY COMPLIANCE REPORT- SECTION C101.5
  
 6) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 SPACE IN ACCORDANCE WITH TABLE 403.1.1, AND INDICATE
 HOW THE OUTDOOR AIR FLOW WILL BE AUTOMATICALLY
 CONTROLLED- SEE SECTION C403.2.4.3 FBC-17 ENERGY
 CONSERVATION. CLARIFY HOW O/A IS BEING SUPPLIED TO THE
 HEAT PUMPS.
  
 7) M1.01.00 SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY
 TRUNKS OF HP-G- SECTION 606.2.1.
  
 8) M1.01.00 & A-4: NON-COMBUSTIBLE DOORS ARE REQUIRED
 FOR THE AC CLOSETS IN COMPLIANCE WITH SECTION 602.2
 FBC-17 MECHANICAL, AND C403.2.9.2 FBC-17 ENERGY
 CONSERVATION.
  
 9) M1.01.00: PROVIDE A SECTION CUT OF THE COVE RETURNS
 THAT SHOWS THE DIMENSIONS OF THE OPENING, AND WHAT
 CONSTRUCTION MATERIALS WILL BE USED- SECTION 602.2
  
 10) M.101.00: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE GAS RANGE, EXHAUST HOOD, AND EXHAUST DUCT. PROVIDE
 A DETAIL SHOWING THE CONNECTION OF THE EXHAUST DUCT
 INTO THE SHAFT.
  
 11) M1.01.00: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE DRYER, AND PROVIDE A DETAIL SHOWING THE CONNECTION
 OF THE EXHAUST DUCT INTO THE SHAFT.
  
 12) M-102.00: PLEASE INDICATE WHICH OF THE SUBDUCT
 DETAILS APPLIES TO THE DRYER EXHAUST, THE TOILET
 EXHAUST, AND THE RANGE EXHAUST.
  
 13) M-102.03: PROVIDE MANUFACTURER'S SPECIFICATIONS FOR
 THE DUCT WRAP WITH SHOP DRAWING APPROVAL STAMP BY THE
 EOR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER