2018-04-06 15:49:50FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-101.00
  
 AT THE END OF MOST LIGHTING CIRCUITS THERE IS ASYMBOL A
 TRIANGLE NOT SHON OF SYMBOL LIST. LIGHTING SYSTEM, IF
 SO NEED CUT SHEETS
  
 MASTER BDROM, STUDY, LIVING RM, DINING RM, FAMILY RM,
 BDRMS 2,3,4 OUTLET SPACING PER CODE E3901.1, E3901.2.2,
 FIXED PANELS
 E3901.2.2 WALL SPACE.
 AS USED IN THIS SECTION, A WALL SPACE SHALL INCLUDE THE
 FOLLOWING: [210.52(A)(2)]
  
 1.ANY SPACE THAT IS 2 FEET (610 MM) OR MORE IN WIDTH,
 INCLUDING SPACE MEASURED AROUND CORNERS, AND THAT IS
 UNBROKEN ALONG THE FLOOR LINE BY DOORWAYS AND SIMILAR
 OPENINGS, FIREPLACES, AND FIXED CABINETS.
  
 2.THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR WALLS,
 EXCLUDING SLIDING PANELS.
  
 3.THE SPACE CREATED BY FIXED ROOM DIVIDERS SUCH AS
 RAILINGS AND FREESTANDING BAR-TYPE COUNTERS.
  
 UTILITY ROOM GFCI, AFCI PER 2014 NEC
 E3902.9 LAUNDRY AREAS.
 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES
 INSTALLED IN LAUNDRY AREAS SHALL HAVE GROUND-FAULT
 CIRCUIT INTERRUPTER PROTECTION FOR PERSONNEL.
 [210.8(A)(9)]
 E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS
  
 KITCHEN OUTLETS
 E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS
  
 BATH OUTLETS FRO TV AND OTHER APPLIANCES
 E3902.7 SINK RECEPTACLES.
 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES
 THAT ARE LOCATED WITHIN 6 FEET (1829 MM) OF THE OUTSIDE
 EDGE OF A SINK SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
 RECEPTACLE OUTLETS SHALL NOT BE INSTALLED IN A FACE-UP
 POSITION IN THE WORK SURFACES OR COUNTERTOPS.
 [210.8(A)(7)]
  
 E3902.8 BATHTUB OR SHOWER STALL RECEPTACLES.
 125-VOLT, SINGLE PHASE, 15- AND 20-AMPERE RECEPTACLES
 THAT ARE LOCATED WITHIN 6 FEET (1829 MM) OF THE OUTSIDE
 EDGE OF A BATHTUB OR SHOWER STALL SHALL HAVE
 GROUND-FAULT CIRCUIT INTERRUPTER PROTECTION FOR
 PERSONNEL. [210.8(A)(8)]
  
 LOAD CALCULATION REQUIRED PER NEC
  
 E3602.1AMPACITY OF UNGROUNDED CONDUCTORS.
 UNGROUNDED SERVICE CONDUCTORS SHALL HAVE AN AMPACITY OF
 NOT LESS THAN THE LOAD SERVED. FOR ONE-FAMILY
 DWELLINGS, THE AMPACITY OF THE UNGROUNDED CONDUCTORS
 SHALL BE NOT LESS THAN 100 AMPERES, 3 WIRE. FOR ALL
 OTHER INSTALLATIONS, THE AMPACITY OF THE UNGROUNDED
 CONDUCTORS SHALL BE NOT LESS THAN 60 AMPERES.
 [230.42(B), 230.79(C) & (D)]
  
 RISER DIAGRAM REQUIRED
  
  