| 2018-04-06 15:49:50 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | PAGE E-101.00 |
| | |
| | AT THE END OF MOST LIGHTING CIRCUITS THERE IS ASYMBOL A |
| | TRIANGLE NOT SHON OF SYMBOL LIST. LIGHTING SYSTEM, IF |
| | SO NEED CUT SHEETS |
| | |
| | MASTER BDROM, STUDY, LIVING RM, DINING RM, FAMILY RM, |
| | BDRMS 2,3,4 OUTLET SPACING PER CODE E3901.1, E3901.2.2, |
| | FIXED PANELS |
| | E3901.2.2 WALL SPACE. |
| | AS USED IN THIS SECTION, A WALL SPACE SHALL INCLUDE THE |
| | FOLLOWING: [210.52(A)(2)] |
| | |
| | 1.ANY SPACE THAT IS 2 FEET (610 MM) OR MORE IN WIDTH, |
| | INCLUDING SPACE MEASURED AROUND CORNERS, AND THAT IS |
| | UNBROKEN ALONG THE FLOOR LINE BY DOORWAYS AND SIMILAR |
| | OPENINGS, FIREPLACES, AND FIXED CABINETS. |
| | |
| | 2.THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR WALLS, |
| | EXCLUDING SLIDING PANELS. |
| | |
| | 3.THE SPACE CREATED BY FIXED ROOM DIVIDERS SUCH AS |
| | RAILINGS AND FREESTANDING BAR-TYPE COUNTERS. |
| | |
| | UTILITY ROOM GFCI, AFCI PER 2014 NEC |
| | E3902.9 LAUNDRY AREAS. |
| | 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES |
| | INSTALLED IN LAUNDRY AREAS SHALL HAVE GROUND-FAULT |
| | CIRCUIT INTERRUPTER PROTECTION FOR PERSONNEL. |
| | [210.8(A)(9)] |
| | E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS |
| | |
| | KITCHEN OUTLETS |
| | E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS |
| | |
| | BATH OUTLETS FRO TV AND OTHER APPLIANCES |
| | E3902.7 SINK RECEPTACLES. |
| | 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES |
| | THAT ARE LOCATED WITHIN 6 FEET (1829 MM) OF THE OUTSIDE |
| | EDGE OF A SINK SHALL HAVE GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. |
| | RECEPTACLE OUTLETS SHALL NOT BE INSTALLED IN A FACE-UP |
| | POSITION IN THE WORK SURFACES OR COUNTERTOPS. |
| | [210.8(A)(7)] |
| | |
| | E3902.8 BATHTUB OR SHOWER STALL RECEPTACLES. |
| | 125-VOLT, SINGLE PHASE, 15- AND 20-AMPERE RECEPTACLES |
| | THAT ARE LOCATED WITHIN 6 FEET (1829 MM) OF THE OUTSIDE |
| | EDGE OF A BATHTUB OR SHOWER STALL SHALL HAVE |
| | GROUND-FAULT CIRCUIT INTERRUPTER PROTECTION FOR |
| | PERSONNEL. [210.8(A)(8)] |
| | |
| | LOAD CALCULATION REQUIRED PER NEC |
| | |
| | E3602.1AMPACITY OF UNGROUNDED CONDUCTORS. |
| | UNGROUNDED SERVICE CONDUCTORS SHALL HAVE AN AMPACITY OF |
| | NOT LESS THAN THE LOAD SERVED. FOR ONE-FAMILY |
| | DWELLINGS, THE AMPACITY OF THE UNGROUNDED CONDUCTORS |
| | SHALL BE NOT LESS THAN 100 AMPERES, 3 WIRE. FOR ALL |
| | OTHER INSTALLATIONS, THE AMPACITY OF THE UNGROUNDED |
| | CONDUCTORS SHALL BE NOT LESS THAN 60 AMPERES. |
| | [230.42(B), 230.79(C) & (D)] |
| | |
| | RISER DIAGRAM REQUIRED |
| | |
| | |