Plan Review Notes
Plan Review Notes For Permit 18030836
Permit Number 18030836
Review Stop B
Sequence Number 1
Notes
Date Text
2018-03-27 11:30:15****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2017 6TH EDITION
  
 1. PERMIT APPLICATIONS SUBMITTED AFTER 12/31/17 SHALL
 BE DESIGNED UNDER THE FLORIDA BUILDING CODE 2017 6TH
 EDITION INCLUDING MECHANICAL, PLUMBING, ENERGY
 CONSERVATION AND ACCESSIBILITY. CHANGE ALL CODE
 REFERENCES THROUGHOUT THE PLANS TO REFLECT THIS UPDATE.
  
 2. PROVIDE ELEVATIONS FOR KITCHEN AND BATHROOM COUNTERS
 SO THAT WE CAN CHECK FOR COMPLIANCE WITH FAIR HOUSING.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. FLOOR SOUND UNDERLAYMENT
  
 1) SUFFOLK CONSTRUCTION TO CONDUCT SITE TESTING FOR
 COMPLIANCE WITH THE 2010 FBC-B SECTIONS:
  
 FBC-B 2010 1207.2 AIR-BORNE SOUND.
 FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
  
 THE SOUND TESTS WILL BE CONDUCTED ON A 10 INCH CONCRETE
 SLAB UNDER THE MAIN PERMIT (15111020) AND SUBMITTED AS
 SOON AS RESULTS ARE PRINTED AND REVIEWED BY THE
 DESIGNER OF RECORD.
 NOTE: SITE TESTING FOR FLOOR INSULATION WILL REQUIRE
 THE APPLICANT TO REQUEST (IN WRITING) UNDER THE 2010 W.
 P. B. ADMINISTRATIVE CODE SECTION 104.11 ALTERNATE
 MATERIALS, DESIGN AND METHODS OF CONSTRUCTION FOR THE
 SOUND UNDERLAYMENT. THE LETTER SHOULD BE MADE OUT TO
 THE BUILDING OFFICIAL ROBERT BROWN.
  
 SHEET: FINISHES. UNIT:
  
 FLOOR FINISHES. BLDG TYPE: TYPE I/ TYPE II FLOOR
 INSULATION (FBC-B 2010)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 10 INCH CONCRETE FLOOR ASSEMBLY AS PER PLAN OR PROVIDE
 ONSITE TESTING TO THE LISTED BELOW ASTM STANDARDS:
  
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4. SHOW FLOOR TRANSITION DETAIL FROM CONDO FLOOR TO
 LOBBY FLOOR.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. IN THE STEAM ROOM WINDOWS ARE SHOWN ON THE EXTERIOR
 WALL OPENING INWARD. HAS THE EXTERIOR ENVELOPE OF THE
 BUILDING CHANGED. PLEASE PROVIDE A DETAIL FOR THIS
 AREA. THERE IS NOT A WINDOW SHOWN ON THE SCHEDULE FOR
 THIS ROOM.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. PROVIDE DETAILS FOR GLASS ENCLOSURES USED AT STEAM
 ROOM, SHOWERS AND TOILET ROOMS. SHOW IF THESE GLASS
 PANELS WILL BE SUPPORTED ON ALL SIDES.
  
 FBC 2403.2 GLASS SUPPORTS.
 WHERE ONE OR MORE SIDES OF ANY PANE OF GLASS ARE NOT
 FIRMLY SUPPORTED, OR ARE SUBJECTED TO UNUSUAL LOAD
 CONDITIONS, DETAILED CONSTRUCTION DOCUMENTS, DETAILED
 SHOP DRAWINGS AND ANALYSIS OR TEST DATA ENSURING SAFE
 PERFORMANCE FOR THE SPECIFIC INSTALLATION SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL.
  
 7. ARCHITECTURAL PAGES NOT DIGITALLY SIGNED.
  
 ARCHITECT DIGITAL SIGNING & SEALING PLANS. 61G1-16.005
 PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR
 ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 (1) INFORMATION STORED IN ELECTRONIC FILES REPRESENTING
 PLANS, SPECIFICATIONS, PLATS, REPORTS, OR OTHER
 DOCUMENTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 481, F.S., SHALL BE SIGNED, DATED AND SEALED BY
 THE ARCHITECT OR INTERIOR DESIGNER IN RESPONSIBLE
 CHARGE.
 (A) A SCANNED IMAGE OF AN ORIGINAL SIGNATURE SHALL NOT
 BE USED IN LIEU OF A DIGITAL OR ELECTRONIC SIGNATURE.
 (B) THE DATE THAT THE ELECTRONIC SIGNATURE FILE WAS
 CREATED OR THE DIGITAL SIGNATURE WAS PLACED INTO THE
 DOCUMENT MUST APPEAR ON THE DOCUMENT IN THE SAME MANNER
 AS DATE IS REQUIRED TO BE APPLIED WHEN A LICENSEE USES
 THE MANUAL SEALING PROCEDURE SET OUT IN RULE
 61G1-16.003, F.A.C.
 (2) AN ARCHITECT OR INTERIOR DESIGNER UTILIZING A
 DIGITAL SIGNATURE TO SEAL CONSTRUCTION DOCUMENTS SHALL
 ASSURE THAT THE DIGITAL SIGNATURE IS:
 (A) UNIQUE TO THE PERSON USING IT;
 (B) CAPABLE OF VERIFICATION;
 (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; AND
 (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE
 ELECTRONIC SIGNATURE IS INVALIDATED IF ANY DATA IN THE
 DOCUMENT ARE CHANGED.
 (3) EACH ELECTRONICALLY SIGNED FILE SHALL HAVE AN
 AUTHENTICATION CODE DEFINED AS A MESSAGE DIGEST
 DESCRIBED IN FEDERAL INFORMATION PROCESSING STANDARD
 PUBLICATION 180-4 ?SECURE HASH STANDARD,? MARCH 2012,
 WHICH IS HEREBY ADOPTED AND INCORPORATED BY REFERENCE
 BY THE BOARD AND CAN BE OBTAINED FROM HTTP://WWW.FLRULE
 S.ORG/GATEWAY/REFERENCE.ASP?NO=REF-01340 OR THE
 INTERNET WEBSITE: HTTP://CSRC.NIST.GOV/PUBLICATIONS/FIP
 S/FIPS180-4/FIPS-180-4.PDF.
  
  
  
  
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  