| Plan Review Notes For Permit 18030817 |
| Permit Number |
18030817 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-03-26 10:18:56 | 1) THE NOTE ON THE HOUSE PLAN STATES THIS IS AN OUTDOOR | | | UNIT BUT THE SUBMITTED HOUSE PLAN IS SO VAGUE IT | | | APPEARS TO SHOW THE UNIT ON THE INTERIOR OF THE HOUSE. | | | CLARIFY. | | | 2) SUBMIT A HOUSE PLAN THAT CLEARLY SHOWS THE LOCATION | | | OF THE WATER HEATER LOCATION IN RELATION TO ALL | | | OPERABLE DOORS AND WINDOES. THE WATER HEATER SHALL BE A | | | MINIMUM OF 4 FEET FROM ANY OPERABLE DOOR OR WINDOW PER | | | THE MANUFACTURER'S INSTALLATION MANUAL. SHOW THIS ON | | | THE PLAN. | | | 3) AN ADDITIONAL PERMIT APPLICATION SHALL BE SUBMITTED | | | FOR THE PLUMBING CONNECTIONS TO THE WATER HEATER. | | | 4) THE INSTALLATION MANUAL SHALL BE ON THE JOBSITE FOR | | | INSPECTION. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|