Plan Review Notes
Plan Review Notes For Permit 18030817
Permit Number 18030817
Review Stop G
Sequence Number 1
Notes
Date Text
2018-03-26 10:18:561) THE NOTE ON THE HOUSE PLAN STATES THIS IS AN OUTDOOR
 UNIT BUT THE SUBMITTED HOUSE PLAN IS SO VAGUE IT
 APPEARS TO SHOW THE UNIT ON THE INTERIOR OF THE HOUSE.
 CLARIFY.
 2) SUBMIT A HOUSE PLAN THAT CLEARLY SHOWS THE LOCATION
 OF THE WATER HEATER LOCATION IN RELATION TO ALL
 OPERABLE DOORS AND WINDOES. THE WATER HEATER SHALL BE A
 MINIMUM OF 4 FEET FROM ANY OPERABLE DOOR OR WINDOW PER
 THE MANUFACTURER'S INSTALLATION MANUAL. SHOW THIS ON
 THE PLAN.
 3) AN ADDITIONAL PERMIT APPLICATION SHALL BE SUBMITTED
 FOR THE PLUMBING CONNECTIONS TO THE WATER HEATER.
 4) THE INSTALLATION MANUAL SHALL BE ON THE JOBSITE FOR
 INSPECTION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  