| Date |
Text |
| 2019-02-11 05:31:09 | 1) A REVISED ORIGINAL PERMIT APPLICATION FOR THE GAS |
| | INSTALLATION MUST BE SUBMITTED. THE GAS PLAN SHOWS A |
| | FUTURE GENERATOR AND A POOL HEATER BUT THESE APPLIANCES |
| | ARE NOT LISTED ON THE GAS APPLICATION. WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 2) THERE ARE TWO DIFFERENT GAS DRAWINGS IN THE PERMIT |
| | SUBMITTAL PACKAGE. REMOVE ALL OLD DOCUMENTS FROM THE |
| | SUBMITTAL PACKAGE AND SUBMIT TWO COMPLETE SETS OF PLANS |
| | SHOWING THE ENTIRE SCOPE OF WORK. WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 3) IDENTIFY THE MODEL OF GENERATOR TO BE INSTALLED ON |
| | THE MANUFACTURER'S SPECIFICATION SHEET. IS IT THE 9 OR |
| | 11 KW? SHOW THE LOCATION OF THE GENERATOR ON THE PLANS. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | FIREPLACE. ONLY THE SPECIFICATIONS FOR THE SHUTOFF |
| | VALVE HAVE BEEN SUBMITTED. EQUIPMENT SHALL BE LISTED |
| | AND LABELED. 2017 FBC-RES. SEC. G2404.3.THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC |
| | SEC.305.1, FBC-RES. SEC.G2408.1. |
| | 5) SUBMIT ADDITIONAL INFORMATION FOR THE GAS DRYER. |
| | WHAT HAS BEEN SUBMITTED INTERNET CONSUMER INFORMATION |
| | AND NOT MANUFACTURER'S SPECIFICATIONS. EQUIPMENT SHALL |
| | BE LISTED AND LABELED. 2017 FBC-RES. SEC. G2404.3. THE |
| | SPEC SHEETS SHALL SHOW THE BTU LOAD OF THE APPLIANCE. |
| | 6) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS |
| | APPLIANCES. 2017 FBC-FUEL GAS SEC. G2407.1, G2439.4, |
| | G2406.2, G2407.5. |
| | 7) ) THE GAS PLAN SHOWS 3 DIFFERENT TYPES OF PIPING |
| | MATERIAL TO BE INSTALLED YET YOU REEFERENCE ONLY ONE |
| | GAS SIZING TABLE WHICH IS FOR PE PIPE. SUBMIT TWO |
| | COPIES OF THE APPLICABLE SIZING TABLES USED TO SIZE THE |
| | GAS SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS |
| | SPECIFYING WHICH SIZING TABLE(S) FROM THE GAS CODE OR |
| | OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS |
| | SYSTEM. REFER TO THE 2017 FBC-FUEL GAS SECS. 401.4, |
| | 401.8, 402.3, AND TABLES 402.4 (1) THRU 402.4 (37) OR |
| | 2017 FBC-RES. SEC. G2413.3, G2412.8, G2413.1, G2413.2, |
| | & G2413.3. |
| | 8) THE GAS SIZING TABLE REFERENCED ON THE PLAN IS FOR A |
| | SYSTEM LESS THAN 2 PSI YET THE GAS DRAWING SHOWS A 2 |
| | PSI SYSTEM. CLARIFY. |
| | 9) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS. |
| | REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING |
| | SHALL BE APPROVED FOR OUTDOOR INSTALLATION. 2014 FGC |
| | SEC.410.1, 2017 FBC-RES. SEC. G2421.1. |
| | 10) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS |
| | SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) |
| | OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES |
| | G2413.4 (1 ) THROUGH G2413.4 (21). |
| | 11) SHOW THE CORRESPONDING EHD OF THE CSST THAT IS |
| | BEING USED AND IDENTIFY THE SIZING TABLE FROM THE GAS |
| | CODE USED TO SIZE THE PIPING. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 12) IDENTIFY ALL THE APPLIANCES ON THE GAS RISER AND |
| | SHOW THE LOCATION OF ALL GAS APPLIANCES AND EQUIPMENT |
| | ON SHEETS A-00 & A-01. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 13) SHT. A-00 SHOWS 2 SEPARATE GAS BRANCH LINES PIPED |
| | TO THE EAST SIDE OF THE STRUCTURE. IDENTIFY THE |
| | APPLIANCE/EQUIPMENT THAT WILL BE CONNECTED TO THESE |
| | LINES. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 14) SHOW THE GAS SHUTOFF VALVES ON THE GAS RISER FOR |
| | THE APPLIANCES. 2017 FBC-RES. SEC. G2420.1. |
| | 15) SHOW THE DISTANCE FROM OUTLET OF THE GAS REGULATORS |
| | TO THE APPLIANCES.WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | **NOTE: I SUGGEST CONTACTING THIS PLAN REVIEWER TO SET |
| | AN APPOINTMENT TO GO OVEERR THESE COMMENTS BEFORE |
| | RESUBMITTING CORRECTIONS. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |